Specifications
9
8.0 SPECIFICATIONS
This Liebert MicroPOD is intended for use with a UPS meeting all the following requirements:
• UPS input cord is compatible with the rating and type of receptacle on the Liebert MicroPOD
labeled UPS.
• UPS output receptacle is compatible with the Liebert MicroPOD input power connector labeled
UPS.
• Available mains receptacle is compatible with the Liebert MicroPOD input power connector
labeled MAINS.”
Table 1 Specifications—Liebert MicroPOD units
Model #
Power Distribution Box Model #
MP2-210K MP2-220L MP2-220K
Used w/ LiebertGXT Rating, VA
700 - 1500 3000 2000
Dimensions, W x D x H, in (mm)
Unit 15.51 x 3.03 x 3.46 (394 x 77 x 88)
Shipping 18.5 x 8.27 x 6.49 (470 x 210 x 165)
Weight, lb (kg)
Unit 4.4 (2.0)
Shipping 6.2 (2.8) 6.6 (3.0)
Electrical Specifications
AC Input
EN60320/C14
receptacle
EN60320/C20
receptacle
EN60320/C20
receptacle
Connection to UPS Input
EN60320/C13
receptacle
EN60320/C19
receptacle
EN60320/C19
receptacle
Connection to UPS Output
EN60320/C14
receptacle
EN60320/C20
receptacle
EN60320/C14
receptacle
Output Receptacles/ Protection
(4) EN 60320/C13 with
10A circuit breaker
(4) EN 60320/C13 with
10A circuit breaker
(2) EN 60320/C13 with
10A circuit breaker
(2) EN 60320/C13 with
10A circuit breaker
(2) EN 60320/C13 with
10A circuit breaker
(1) EN 60320/C19 with
16A circuit breaker
(4) EN 60320/C13 with
10A circuit breaker
(4) EN 60320/C13 with
10A circuit breaker
Table 2 General characteristics—Liebert MicroPOD units, pluggable and hardwire
Transfer Time (to and from maintenance bypass) < 6 milliseconds
Operating Ambient Temperature 32°F to 104°F (0°C to +40°C)
Storage Ambient Temperature -4°F to 140°F (-20°C to +60°C)
Humidity 0 to 95% non-condensing
Agency/Standards UL 1778, c-UL, ISTA Procedure 1A