Chapter 4 Use Of Monitoring Module M500D 33
Enter New PWD:
000000
Input Again!
Use “▼” or “▲” to change the number, and “◄” or “►” to move the cursor left or right. Press “ENT” to confirm. You
should input the same number twice to complete the setting.
4. The value description of the parameters is listed below:
Table 1.1 System setting parameter description
Parameter Range Default Value description
Text
Chinese,
English and
Spanish
Chinese Set according to your need
Address 1 ~ 254 1
The addresses of power systems that are at the
same monitored office should be different
CommMode
MODEM, EEM-
M, RS-232
RS-232
“MODEM”: Through modem and based on the
Telecom protocol.
“EEM-M”: Through modem and based on the EES
protocol.
“RS-232”: Through a transparent serial port and
based on the Telecom protocol
BaudRate
1200bps,
2400bps,
4800bps,
9600bps
9600bps
Make sure the baud rates of both the sending and
receiving parties are the same
Set Date 2,000 ~ 2,099 Set the time according to the current actual time,
regardless of whether it is a leap year or not
Set Time Hour, min, sec
Operator
level or
above
Init PWD
(initialize
password)
Y, N N
Selecting “Y” can reset the user level and
administrator level passwords to the defaults
Init Param
(initialize
parameters)
Y, N N
When the system parameters cannot be set
normally, and the usual resetting methods do not
work, you can set the “Init Param” to Y, and all the
system parameters will be restored to defaults.
Alarms may be raised for the defaults may fail to
meet the actual situation. Set the parameters
according to the actual situation then
Operator
level or
above
System
Type
NetSure 501 A50:
48V/30A/SET/NONE;
NetSure 701 A51
(PS48300-3A/3200):
48V/50A/300/ NONE;
NetSure 701 A51
(PS48300-3A/3200-
X2):
48V/50A/SET/NONE;
NetSure 501 AA0:
48V/30A/300/NONE
This parameter has been set according to the actual
situation upon delivery and needs not to be
changed. However, when a new monitoring module
is used, its “System Type” should be set according
to the actual situation.
After this parameter is changed, the monitoring
module will restart automatically, and other
parameters of the monitoring module will be
changed to the defaults of the corresponding
system type. You should change some parameters
according to the actual situation
Administrator
Change
Password
User, Operator,
Admin
The password can be 6 digits long at most
Con Alarm
Voice
3min, 10min, 1h,
4h, constant
Contstant The period that an alarm sound will last
Serial The production serial No. of the monitoring module. This parameter cannot be changed
SW Ver The software version No. of the monitoring module. This parameter cannot be changed
Set Enable
Reflecting the jumper status of a hardware switch within the monitoring module. If this parameter is
set to ”N”, you are not allowed to use the jumper, nor change any parameter except the battery
management mode. The maintenance over the monitoring module will not be affected
NetSure 501 A50, NetSure 501 AA0, NetSure 701 A51 19-Inch Subrack Power Supply System User Manual

Table of Contents

Other manuals for Emerson NetSure 501 A50

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson NetSure 501 A50 and is the answer not in the manual?

Emerson NetSure 501 A50 Specifications

General IconGeneral
BrandEmerson
ModelNetSure 501 A50
CategoryPower Supply
LanguageEnglish

Related product manuals