Parameter 03.007 At Speed Upper Limit
Short description Set to the required maximum at speed threshold
Mode OpenLoop
Minimum 0.0 Maximum 550.0
Default 1.0 Units Hz
Type 16 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 1
Coding RW
See At Speed Lower Limit (03.006).
Parameter 03.008 Over Speed Threshold
Short description Set to the required over speed threshold
Mode OpenLoop
Minimum 0.0 Maximum 550.0
Default 0.0 Units Hz
Type 16 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 1
Coding RW
If Over Speed Threshold (03.008) is set to a non-zero value it defines the over speed threshold. If the Post Ramp Reference (02.001) exceeds this
threshold in either direction an Over Speed trip is produced. If Over Speed Threshold (03.008) is set to 0.0 the threshold is based on the variable
minimum/maximum for the references and is equal to 1.2 x VM_SPEED_FREQ_REF[MAX].
Parameter 03.009 Absolute At Speed Select
Short description Indicates when the motor is running at speed
Mode OpenLoop
Minimum 0 Maximum 1
Default 0 Units
Type 1 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 0
Coding RW
See At Speed Lower Limit (03.006).
Powerdrive F300 Parameter Reference Guide
Issue: 01.15.00
51