Quick Start Guide Section 5
GFK-2893P Sep 2019
Product Certification & Installation Guidelines 35
Description
Agency
Marking
Comments
7, 10, 12, 15” units
only.
5.2 Conditions of Safe Use for
Installation in Hazardous Locations
The following information applies to products bearing
the UL marking for Hazardous areas and the ATEX
marking for Zone 2 explosive atmospheres:
Suitable for use in Class I Division 2 Groups A, B, C,
D; Class 2 Division 2 Groups F, G; Class 3 Division 1
and Division 2.
Suitable for Group II, Category 3, Gas Groups IIC,
Dust Group IIIC (applicable only to the
IC755CSW07CDACA, IC755CSS10CDACA,
IC755CSS12CDBCA, and IC755CSS15CDACA Display
units):
1. The equipment shall only be used in an area of at
least pollution degree 2, as defined in IEC 60664-1.
Note: Pollution degree 2 can be achieved when the
installation is in a controlled environment with suitably
controlled condensation or airborne pollution.
2. The equipment shall be installed in an enclosure
that provides a minimum ingress protection of IP
54 in accordance with IEC 60079-0.