Unidrive M200-201 Quick Start Guide 41
Issue Number: 6
Defines the functionality of Analog Output 1.
Defines the maximum switching frequency that can be used by the drive.
See the Drive User Guide for drive derating data.
00.036 {07.055} Analog Output 1 Control
RW Txt US
OL
Ú
0 to 14
Ö
0
RFC-A
Value Description
0 User defined by Analog Output 1 Source A
1 Frequency output
2 Frequency reference
3 Motor speed
4 Current Magnitude
6 Torque output
7 Torque current output
8 Voltage output
9 DC bus voltage (0~800 V)
10 Analog Input 1
11 Analog Input 2
12 Power output (0~2 x Pe)
13 Torque limitation
14 Torque reference (0~300 %)
00.037 {05.018} Maximum Switching Frequency
RW Txt US
OL
Ú
0.667 (0), 1 (1), 2 (2), 3 (3), 4 (4),
6 (5), 8 (6), 12 (7), 16 (8) kHz
Ö
3 (3) kHz
RFC-A
2 (2), 3 (3), 4 (4), 6 (5), 8 (6), 12 (7),
16 (8) kHz
Pr 00.037 Text Description
0 0.667 667 Hz switching frequency
1 1 1 kHz switching frequency
2 2 2 kHz switching frequency
3 3 3 kHz switching frequency
4 4 4 kHz switching frequency
5 6 6 kHz switching frequency
6 8 8 kHz switching frequency
7 12 12 kHz switching frequency
8 16 16 kHz switching frequency