EasyManua.ls Logo

Emerson unidrive m300 - Page 37

Emerson unidrive m300
58 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Unidrive M300/HS30 Quick Start Guide 37
Issue Number: 6
Defines how the motor is controlled when the run signal is removed from the drive.
See the Drive User Guide for further information.
Set to 1 to enable Dynamic V to F mode.
0: Fixed linear voltage to frequency ratio (constant torque - standard load)
1: Voltage to frequency ratio dependant on load current. This gives a higher motor efficiency.
If the drive is to be configured in fixed boost mode (Pr 00.041 = Fd or SrE) with catch a spinning
motor software enabled, an autotune (see Pr 00.038 on page 40) must be carried out to measure the
motor's stator resistance beforehand. If a stator resistance is not measured, the drive may trip on 0 V
or OI.AC while trying to catch a spinning motor.
00.031 {06.001} Stop Mode
RW Txt US
OL
Ú
CoASt (0), rP (1), rP.dc I (2),
dc I (3), td.dc I (4), dis (5)
Ö
rP (1)
RFC-A
CoASt (0), rP (1), rP.dc I (2),
dc I (3), td.dc I (4), dis (5), No.rP (6)
Value Text Description
0 Coast Coast stop
1 rp Ramp stop
2 rP.dcI Ramp stop + 1 second dc injection
3 dc I Injection braking stop with detection of zero speed
4 td.dcI Timed injection braking stop
5 Dis Disable
6 No.rP No ramp (RFC-A mode only)
00.032 {05.013} Dynamic V To F Select / Flux Optimisation Select
RW Num US
OL
Ú
0 to 1
Ö
0
RFC-A
00.033 {06.009} Catch a Spinning Motor
RW Txt US
OL
Ú
dis (0), Enable (1), Fr.Only (2),
Rv.Only (3)
Ö
dis (0)
RFC-A
Pr 00.033 Text Function
0 Dis Disabled
1 Enable Detect all frequencies
2 Fr.Only Detect positive frequencies only
3 Rv.Only Detect negative frequencies only
Unidrive M300 Quick Start Guide English Iss6.book Page 37 Tuesday, September 22, 2015 3:21 PM

Other manuals for Emerson unidrive m300

Related product manuals