4.2.5Inputs
Note : Thesesensortypescanonlybeusedinthe Trans-AMF.RS485units.
TheUSBcommunicationinterfacecannotbeusedwhenoneofthesesensortypesis
selected.
*
1
Min
Default
Unit
SENDER INPUTS ( )Inputs->Sender inputs
Max
OilPressureInput Type
OilPressurePre-Alarm
OilPressurePre-AlarmReset
Coolant TemperatureInput Type
1.2
0.0(dis) 30.0
BAR
1.4
0.0 30.0
BAR
1.0
0.0 30.0
BAR
0-NotUsed(Disable)
1-DigitalNC
2-DigitalNO
3-VDO5BAR
4-VDO7BAR
5-VDO10BAR
6-DATCON5BAR
7-DATCON7BAR
8-MURPHY 7BAR
9-UserConfigured
90
0(dis) 300
88
0 300
95
0 300
TemperatureSensorBreak
High TemperaturePre-Alarm
OilPressureShutdown
High Temp.Pre-AlarmReset
High TemperatureShutdown
C
C
C
Temp. sensor break
High temp. prealarm
High temp. reset
High temp. shutdown
Conf. AI1 type
Temp. input type
Oil pressure shutdown
Oil pressure reset
Oil pressure prealarm
Oil press. input type
0 (dis)
70
Low TemperatureWarning
C
Low temp. warning
Conf. AI1 unit
Configurable AnalogInput-1 Type
0(dis)
0-NotUsed(Disable)
1-DigitalNC
2-DigitalNO
3-
4- 5
5-DATCON
6-MURPHY
7-PT100
8-UserConfigured
VDO120ºC
VDO1 0ºC
0(dis)
0-NotUsed(Disable)
1-DigitalNC
2-DigitalNO
3-VDOOHM(10-180)
4-VDO TUBE(90-0)
5-USOHM(240-33)
6-ELS11OHM(0-190)
7-FORD(73-10)
8-ELS13OHM(0-190)
9-ELS30OHM(0-190)
10-DAVITEQ(RS485)
11-KUSCLS2(RS485)
12-MSLL 790(RS485)
13-CSFL 790(RS485)
14-UserConfigured
*
1
*
1
*
1
*
1
0(dis)
0(dis)
OilPressureUnit
Oil pressure unit
BARBAR/PSI/KPA
Coolant TemperatureUnit
Temperature unit
ºCºC/ºF
BAR/PSI/KPA/ºC/ºF/%/Lt
%
Configurable AnalogInput-1Unit
0(dis)
0 (dis) 300
CoolantHeaterControlOn
C
Heater control ON
0
300
CoolantHeaterControlOff
C
Heater control OFF
45
5
0 9999
WaterPumpOn Time
Water pump on time
0
9999
WaterPumpOff Time
Sec
Water pump off time
5
Sec
0-Disable
1-EnableFromSafety
On(3min.delayed)
2- AlwaysEnable
0(dis)