26
Min
Default
START TIMERS ( )Timers->Start timers
Max
Mains TransientDelay
RemoteStartDelay
Pre-Heat
2.0
Pre-HeatBypass
0.0 20.0
4
0 3600
3
0 250
0
0 250
SafetyOnDelay
5
0 99
HornDuration
60
0(dis) 999
ChargeExcitation Time
15
0 99(cont)
CoolingFan Time
180
0 250
Remote start delay
Pre-heat
Pre-heat bypass
Safety on delay
Horn duration
Chg. excitation time
Cooling fan time
Mains transient delay
MainsFailStartDelay
0
0 9999
Mains fail start dely
Unit
Sec
Min
Sec
Sec
Sec
Sec
Sec
Sec
Sec
IdleMode Time(SmokeLimiting)
dis
3600
Idle mode time
IdleMode TimeOff(SmokeLimitingOff)
Idle mode time off
Sec
Sec
0(dis)
0 250 5
4.2.7Timers
Warmup Time
3
0 250
Warming up time
Sec
Note: dis=disablecont=continuous
Min
Default
STOPPING TIMERS ( )Timers->Stopping timers
Max
RemoteStopDelay
Cooling Time
4
0 250
60
0(dis)
3600
Fail ToStop Time
BatteryCharging eTim
IdleStop eTim
30
5
dis
15
1
0(dis)
999
9999
3600
Remote stop delay
Cooling time
Fail to stop delay
Battery charging time
Idle stop time
Unit
Sec
Sec
Sec
Min
Sec
MainsReturnDelay
5
0 3600
Mains return delay
Sec
4.2.8ExpansionModules
IO (1-8) MODULE ( )Expansion modules->IO (1-8)
ExpansionI/OModuleSelection
Disable/enable select
Min
Default
Max
DISBL
ENABL/DISBL
Unit
DIAL-UP & ETHERNET ( )Expansion modules->Dial-up & Ethernet
Expansion ModuleSelectionDal-up&Ethernet
CallBack Selection
Disable/enable select
Call back selection
Min
Default
Max
ENABL
DISBL
ENABL/DISBL
ENABL/DISBL
Unit
Min
Min
Default
Default
Unit
Unit
Max
Max
0
0
1
1
0
0
138
138
0
0
12
12
ThesameasConfigurableOutput-1options
ThesameasConfigurableOutput-1options
CONF. EXP. OUTPUT-7 ( )Outputs->Conf. exp. output-7
CONF. EXP. OUTPUT-8 ( )Outputs->Conf. exp. output-8
Polarity
Polarity
Function
Function
0-NormallyOpen(Close To Activate)
1-NormallyClose(Open To Activate)
0-NormallyOpen(Close To Activate)
1-NormallyClose(Open To Activate)
GPRS MODULE ( )Expansion modules->GPRS
Expansion ModuleSelectionGPRS
CallBack Selection
Cellinforefreshrate
Locationdata
Locationwarning
Disable/enable select
Call back selection
Cell inf refresh rate
Location data
Location warning
Min
Default
Max
1- SERVERGPRS
DISBL
2
1(dis)
0-DISABLE
1- SERVER
2- CLIENT
3-SMS
GPRS
GPRS
ENABL/DISBL
0(dis)
1(dis)
Unit
999
999
Min
Km
DISBL
ENABL/DISBL