EasyManua.ls Logo

EMKO TRANS-AMF - Page 28

EMKO TRANS-AMF
29 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
28
5.Specifications
Equipmentuse
Housing&Mounting
PanelCut-Out
Protection
Weight
Environmentalrating
Operating/StorageTemperature
Operating/StorageHumidity
Vibration
Shock
InstallationOverVolt.Category
PollutionDegree
ModeofOperation
CrankingDropouts
BatteryVoltageMeasurement
MainsVoltageMeasurement
MainsFrequency
GeneratorVoltageMeasurement
GeneratorFrequency
MagneticPickupInput
CTsecondary
ChargeGeneratorExcitation
ChargeGen.Vol.Measurement
SenderMeasurement
CanbinTemp.Measurement
Communicationinterface
OptionalExpansionI/OModule
OptionalComm.Modules
:Electricalcontrolequipmentforgeneratingsets.
:229mmx152mmx41mm.(includingconnectors)
.
:182mmx135mm.
:
: Approximately0,53Kg.
:
withnon-condensinghumidity
:-20°Cto+70°C/-30°Cto+80°C
:95%max.(non-condensing)
:EN60068-2-6
Tensweepsineachofthreemajoraxes
5Hzto8Hz@+/-7.5mm,8Hzto500Hz@2gn.
:EN60068-2-27
Threeshocksineachofthreemajoraxes
15gnin11mS.
:II Appliances,portableequipment
:II,Normalofficeorworkplace,nonconductivepollution
:Continuous.
:8to32V (Peak:36V ).Max.operatingcurrentis360mA.
:Batteryvoltagecanbe“0”VDCformax.50msduring
cranking(batteryvoltageshouldbeatleastnominal
voltagebeforecranking).
:8to32V ,accuracy:1%FS,resolution:0,1V
:10
Resolution:1V,Harmonics:Upto11
th
.
:5to99.9Hz(min.20VACPh-N) Accuracy:0,25%FS,
Resolution:0,1Hz.
:10
Resolution:1V,Harmonics:Upto11
th
.
:5to99.9Hz(min.20VACPh-N) Accuracy:0,25%FS,
Resolution:0,1Hz.
:35to10000Hz(1to35voltspeakcontinuously).
Accuracy:0,25%FS.
:5A.
:210mA @12V,105mA @24V.Nominal2.5W.
:8to32V ,accuracy:1%FS,resolution:0,1V.
:0to1300ohm,accuracy:1%FS,resolution:1ohm.
:-50to+100ºC,accuracy:1%FS,resolution:1ºC.
:USBprogrammingandcommunicationport,RS-485(optional),
CanBuscommunicationwith1939ECU.
:ExpansionI/Omoduleincluding8inputsand8outputs.
:Ethernet/Dial-up,GSM/GPRS,RS-232/485/422,DualSet,
WebServerandGPRS-Webmodules.
.Plastic
housingforpanelmounting
IP65atfrontpanel.
Standard,indooratanaltitudeoflessthen2000meters
.
to300VACPh-N,5to99.9Hz. Accuracy:1%FS,
to300VACPh-N,5to99.9Hz. Accuracy:1%FS,
DCBatterySupplyVoltage Z Z
Z
Z

Other manuals for EMKO TRANS-AMF