74
Malfunction
A part of the information and instructions
may be provided in close detail, so that ...
...the texts may well
take several screens.
Appropriate instructions appear
for each source of faults.
Perform the measure in accordance
with the recommendation.
Continue with ›Explanation‹.
1.10 Service Wizard
04. 07. 2012 10:34
Please check
the sensor for
plausible values.
Explanation
1.10 Service Wizard
04. 07. 2012 10:34
Disconnect it
and measure
its resistor.
Next
1.10 Service Wizard
04. 07. 2012 10:34
With PT 1000 sensors
0°C to 100°C
correspond to
a resistor of
1000 to 1385 Ohm.