Device configuration, application setup Graphic Data Manager
22
"Batch 1-4" submenu Batch-specific settings.
Fig. 4: Setup - Application - Batch mode, "Batch x" submenu
Description Enter a unique description for the batch here (recommended when
several batches are running in parallel on the device.) If no data are
entered, the device generates a description automatically. Text entry:
max. 16-digit.
16060/000 to
16060/003
Start/stop Specify how batches are started/ended.
"Per control input": the batch is started/ended externally via a digital
control input (effect: start/stop batch x).
"At device/barcode/fieldbus": the batch can be started/ended by
operating the device, using a barcode or remotely (PC software,
fieldbus).
"Preset counter": the batch can be started by operating the device, using
a barcode reader or control input. The batch is ended when the counter
value >= the default value.
16061/000 to
16061/003
Control input
only if "Start/stop" - "Preset
counter"
Select the control input that starts the batch. Alternatively, the batch can
be started via on-site operation.
!
Note!
The batch cannot be ended using this input. The assigned input is
automatically pre-configured!
Picklist: Switched off, Digital input x
16069/000 to
16069/003
Control input
only if "Start/stop" - "Per control
input"
Select the control input that starts/ends the batch.
!
Note!
The assigned input is automatically pre-configured!
The input must be active during the batch. The minimum duration of the
batch is one second.
Picklist: Switched off, Digital input x
16062/000 to
16062/003
Preset counter
only if "Start/stop" - "Preset
counter"
Select the counter that ends the batch.
!
Note!
The assigned input is automatically pre-configured!
Picklist: Switched off, Analog input x, Digital input x, Maths x
16062/000 to
16062/003
Switches relay The assigned relay is switched as long as the batch is running.
Picklist: Not used, Relay x (xx-xx)
16065/000 to
16065/003
"Application -
Batch mode"
menu items
Configurable parameters
(factory settings are highlighted in bold)
Direct access
code

Related product manuals