TERMINAL DESCRIPTIONS
HEATING COOLING VERSION
Terminal changes when using SH(X) humidifier version are indicated.
ECM motor output controls signal
ECM motor speed feedback signal
Hot water coil valve actuator.
Chilled water coil valve actuator. 0V=off.
Economizer / Mixbox actuator. 0V=closed.
AO
Modulating profile pressure damper actuator
output.
0-10 Vdc
Alarm contact for annunciation.
Two position actuator control.
CMa COM
‘a’
Common power relays ‘a’, above. 24/120 Vac
CMb COM
‘b’
Common power relays ‘b’, below. 24/120 Vac
STG1 DO Cooling stage #1
stage #1 cooling, powered from
common ‘b’.
24/120 Vac
STG2 DO Cooling stage #2
common ‘b’.
24/120 Vac
STG3 DO Cooling stage #3
common ‘b’.
24/120 Vac
STG4 DO Cooling stage #4
common ‘b’.
24/120 Vac
STG5 DO Cooling stage #5
common ‘b’.
24/120 Vac
High speed fan start contact
DO
contact.
24/120 Vac
CMc COM
‘c’
Common power relays ‘c’, below. 24/120 Vac
Modulating gas valve actuator output.
MCA AO
air
Modulating combustion air actuator output. 0-10 Vdc
FbG AI Feedback Gas
Compares the ball valve actuator feedback
signal to the demand signal.
0-10 Vdc