Power Factor Controller
BR 7000
Manual
Version 1.1 E
Power Factor
Controller
BR 7000
Auto
Program
Manual
Service
Enter
OK
Power Quality Solutions
HELP
ESC
AUTO-MODE 2/2
14
137
140
kvar
kW
kVA
Q
P
S
cos
ϕ

Questions and Answers

  • M
    melissa03Aug 2, 2025
    What to do if the Epcos Controller system permanently switches capacitors on and off?
    • C
      Caleb BooneAug 3, 2025
      If the Epcos Controller system is constantly switching capacitors on and off, even when the load remains stable (system oscillating), the programming and the values of the current converters should be checked.
  • R
    rebeccalucasAug 9, 2025
    What to do if the Epcos Controller does not connect all stages?
    • L
      Lauren DiazAug 9, 2025
      If the Epcos Controller isn't connecting all stages, or the cos-phi value doesn't change at the last stages, examine the END STOP and CONTROL-MODE settings. Also, verify that specific steps haven't been programmed as fixed steps or as OUT in the menu for manual operation/fixed steps.
  • S
    singletonmichelleAug 15, 2025
    Why is the wrong cos Phi displayed on my Epcos Controller?
    • A
      Antonio HansonAug 15, 2025
      If the cos Phi displayed is incorrect, check the terminals of the measuring voltage and measuring current (l and k), verify the phase position, and ensure correct phase allocation, confirming that voltage and current are in the same phase.
  • C
    chasedwayneAug 20, 2025
    What to do if outputs are switched off in stages irrespective of power line conditions in Epcos Controller?
    • Q
      qrodriguezAug 20, 2025
      If the outputs are being switched off in stages regardless of the power line conditions, check the grid conditions. If it is permissible, consider increasing the threshold TDH-V (7%).
  • C
    Cristian BrownAug 27, 2025
    What to do if there is no current in measuring range of Epcos Controller?
    • A
      Anna DavisAug 27, 2025
      To address a situation where there's no current in the measuring range, a line interruption, a wrong current-converter factor, or a short-circuited current transformer, check the ratio of the current transformer (1/5A), go through the measuring current range, and check the connections and phase position.

Summary

Section 2: INSTALLATION AND INSTRUCTIONS FOR USAGE

Section 3: CONNECTION ALTERNATIVES MEASURING VOLTAGE AND MEASURING CURRENT

Section 6: PROGRAM-MODE (manual programming)

6.2 QUICK-PROGRAM

Facilitates fast programming of essential parameters for the BR7000.

Section 7: AUTOMATIC INITIALIZATION

Section 8: AUTOMATIC TEST RUN

Section 9: HELP-Functions; actual output assignment

Section 10: MANUAL OPERATION

Section 11: SERVICE MENU; Fault memory

Section 12: EXPERT-MODE 1 and 2

12.1 EXPERT-MODE 1 (Code: 6343)

Accesses advanced settings for system configuration and operations with a specific password.

12.2 EXPERT-MODE 2 (Code: 2244)

Configures operational, warning, and fault messages with a specific password.

Section 13: CONTROL PRINCIPLE

Section 14: INTERFACES

Section 15: ALARM RELAY; ERROR MESSAGES

Annex 1: Troubleshooting

Annex 5: MODBUS-Protocol - Part 1: read-only registers ( Functioncode 3)

Epcos BR 7000 Specifications

General IconGeneral
BrandEpcos
ModelBR 7000
CategoryController
LanguageEnglish