EasyManua.ls Logo

Epcos BR 7000 - Page 10

Epcos BR 7000
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Section 5: DISPLAY OF GRID PARAMETERS
5.1 Display of 3 selected grid parameters
In Auto-Mode, button é leads to display mode 1. Here 3 (free selectable) grid parameters
are displayed in large letters. The selection and storage of these values is done in the
Display- Editor.
Example: Display mode 1:
Desired values selected in the
Display Editor (see section 16 )
5.2 Display of particular grid parameters (from AUTO-MODE by pressing ENTER)
By repeated activation of the “ENTER”-button (in automatic operation) several grid
parameters can be displayed (s. table below):
Action Display Unit in% large display Bargraph 3-phase
possible possible
ENTER 1 LINE VOLTAGE V x x
ENTER 2 APPARENT CURRENT A x x x
ENTER 3 REACTIVE POWER kvar x x x
ENTER 4 ACTIVE POWER kW x x x
ENTER 5 APPARENT POWER kVA x x x
ENTER 6 DIFF. kvar to target kvar x x x
ENTER 7 FREQUENCY Hz x x
ENTER 8 TEMPERATURE °C / °F x
ENTER 9 3.-31. HARMONICS V/ I x x x
ENTER 10 HARMONICS THD-V/I x x x
ENTER 11 Comp.- power (only at real capacitor current measurement)
ENTER 12 ENERGY kvarh / kWh
ENTER 13 TIME / DATE é / ê change the date format
ENTER 14 Software version
ENTER return to: 1
Buttons é / ê change the display format:
The values can be displayed in their unit, in % or as large display resp. bar chart.
Examples, see next page.
- 9 -
AUTO-MODE 2/2
14
137
140
kvar
kW
kVA
Q
P
S