BR 7000 rear view
Operating mode:
- Automatic
- Program.
- Manual oper.
- Service
- Expert Mode
- Osci - Mode
- Display Editor
ENTER/ OK
Confirmation
storage of
values
Increase
selected
parameter
HELP
opens
Help pages
Reduce
selected
parameter
Escape
previous
page/value
in the display
- 5 -
BR 7000 front view
The controller is supplied for a standard operating voltage of 110...230VAC (+/-15%), a
measuring voltage of 30...440 V~ (L-N) resp. 50...760V~ (L-L), 50/60Hz, and a
measuring current of 5A or 1A (programmable). A voltage converter is required for
different operating voltages.
Caution!
Voltages which exceed the allowed voltage range can damage the
device !
!
Power Factor
Controller
BR 7000
Auto
Program
Manual
Service
Enter
OK
Power Quality Solutions
HELP
ESC
HELP
ESC
Power factor controller BR7000
Type: BR7000-R
Meas voltage: 50 - 760VAC 50/60Hz
Supply voltage:110 - 230VAC 50/60Hz
Ser.Nr.: 0815 / 2009
P1
P2
P3
K1
K6
K11
K2
K7
K12
K3
K8
K13
K4
K9
K14
K5
K10
K15
K21
K22
K23
Meas.current
k L1 l
Supply voltage
110...230V~
Measuring voltage
30 ... 440V L-N
Output 11-15
Output 6-10
Output 1-5
Switching outputs:
Fan relay
Message relay
Alarm relay
Meas.current
k L2 l
Meas.current
k L3 l
Interface 1
Contact assignment 2nd terminal at bottom
Interface 2
External input
230V~
GND B A PE
L1 N L1 L2 L3 N
The allocation of switching outputs K1…K15
to the capacitors complies to the selected
connection variant and the desired
CONTROL-MODE
(Programming/point 2)
Especially in ”Mixed Mode“ where some
outputs are used for single phase capacitors,
others for 3-phase-capacitors the proper
connection must be assured!
In the “HELP”-menu the BR7000 directly
displays the actual correct allocation of
outputs (AUTO-MODE: Help-page 7-9).
For examples also see chapter 9.
cos
ϕ