EasyManua.ls Logo

Epsolar MT50 - Control Parameter Table; Battery Voltage Parameters

Epsolar MT50
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Control voltage parameters
Gel Sealed Flooded User
16.0V 16.0V 16.0V 9~17V
15.0V 15.0V 15.0V 9~17V
15.0V 15.0V 15.0V 9~17V
—— 14.6V 14.8V 9~17V
14.2V 14.4V 14.6V 9~17V
13.8V 13.8V 13.8V 9~17V
13.2V 13.2V 13.2V 9~17V
12.6V 12.6V 12.6V 9~17V
Warning Reconnect
12.2V 12.2V 12.2V 9~17V
12.0V 12.0V 12.0V 9~17V
11.1V 11.1V 11.1V 9~17V
10.6V 10.6V 10.6V 9~17V
——
2 hrs.
2 hrs.
0~3 hrs.
2 hrs.
2 hrs.
2 hrs.
0~3 hrs.
18
19
书籍1.indb 18 2013-10-18 15:04:21