EasyManua.ls Logo

Ericsson RBS 2206 - DC to 60 V DC Power

Ericsson RBS 2206
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RBS Product Description
RBS 2206 +24 V DC Fuses
Table 13 Fuse Specifications
Minimum for Safe
Function
Recommended for
Maximum Selectivity
Maximum Allowed
Fuse Rating
1 × 160 A
(1)
1 × 200 A 1 × 250 A
(1) Can be used when no transmission or optional equipment is installed.
RBS 2206 V2 +24 V DC Fuses
Table 14 Fuse Specifications
Minimum for Safe
Function
Recommended for
Maximum Selectivity
Maximum Allowed
Fuse Rating
1 × 160 A 1 × 200 A 1 × 300 A
8.3
0
48 V DC to
0
60 V DC Power
Table 15 Requirements
Characteristic
Description
Nominal
0
48 or
0
60 V DC
Range
0
40.0 to
0
72.0 V DC
Non-destructive range +0 to
0
80 V DC
Inrush current 200 A (0.1–5 ms)
RBS 2206
0
48 V DC to
0
60 V DC Fuses
Table 16 Fuse Specifications
Minimum for Safe
Function
Recommended for
Maximum Selectivity
Maximum Allowed
Fuse Rating
4 × 32 A 4 × 35 A 4 × 40 A
RBS 2206 V2
0
48 V DC to
0
60 V DC Fuses
Table 17 Fuse Specifications
Minimum for Safe
Function
Recommended for
Maximum Selectivity
Maximum Allowed
Fuse Rating
3 × 45 A 3 × 50 A 3 × 50 A
28 19/1551-LZA 701 0001 Uen PG1 | 2010-10-08