GB
Activate Alternative temperature
Alternative temperature is activated by external equipment
such as an external watch or a GSM module for example
ESBE GSM module CRB915, art.number 1705 59 00.
1. Disconnect power to the controller.
2.Unscrew the cover and remove it (A), connect the two
conductors to the
connector (B).
3. Assembly the cover back
4. Connect power to the controller (C).
When the two conductors are interconnected the
alternative temperature is activated and the
T2 symbol
is shown in the display. The connection shall be without
any voltage or current and with a maximum resistance of
100Ω. (D)
DE
Aktivieren der alternativen Solltemperatur
Die alternative Solltemperatur wird über externe Komponenten
aktiviert, beispielsweise über einen Schalter, eine externe Uhr
oder das ESBE GSM-Modul CRB915 (Art.Nr.:17055900).
1. Trennen Sie den Regler von der Stromversorgung.
2.Schrauben Sie die Abdeckung ab (A) und schließen Sie die
beiden Leiter an
an. (B).
3. Montieren Sie die Abdeckung wieder.
4. Stellen Sie die Stromversorgung wieder her (
C).
Wenn die beiden Leiter miteinander verbunden werden, wird
die alternative Solltemperatur aktiviert und
T2 erscheint im
Display. An dieser Verbindung darf weder Spannung noch Strom
anliegen und sie darf einen maximalen Widerstand von 100Ω
aufweisen (D).
T2
N
24V∼
24V∼
Open
Close
ActuatorSupply
Remote Temp.sensor
A
B
7
Alternative temperature