Page 1 of 10 D A T A S H E E T 85005-0131
Not to be used for installation purposes. Issue 7
EST Catalog u Small Building Fire Alarm Solutions
06-27-13
Overview
The Edwards EST iO64 intelligent life safety system offers the
power of high-end intelligent processing in a configuration that
delivers an uncomplicated solution for small to mid-sized applica-
tions. With intelligent detection, electronic addressing, automatic
device mapping, optional Ethernet
®
connectivity, and a full line of
easily-configured option cards and modules, this flexible system
offers advanced features that benefit building owners and contrac-
tors alike.
The iO64 provides one Class B analog device loop that supports
up to 64 device addresses, and two Class B Notification Appli-
ance Circuits (NACs). Optional Class A device wiring is available
with the use of a module.
This life safety system features an attractive design that fits with
any decor. Its distinctive doorfront offers a contemporary look
that’s available with red or silver finishes. All LED indicators and its
large backlit display remain easy to see at all times.
The iO64 supports a wide range of accessories and related equip-
ment, including:
Signature Series intelligent modules, detectors, and bases
R-Series remote annunciators
option cards that expand system capacity and extend system
capabilities
fully integrated CO detection using Signature Series 2 detec-
tors with or w/o audible signaling.
Features
Comes standard with one loop that supports up to 64
intelligent devices of any type and two Class B NACs.
Supports Signature Series modules and detectors
Combines the Signature intelligent releasing module with
Signature multisensor detectors for reliable suppression
Form C for Alarm and Trouble, Form A for Supervisory
Electronic addressing with automatic device mapping
Optional Ethernet port for diagnostics, programming and
variety of system reports
Two programmable switches with LEDs and custom labeling
Supports Genesis horn silence over two wires and UL
1971-compliant strobe synchronization
Supports up to eight serial annunciators, (LCD, LED-only, and
graphic interface).
Can use existing wiring for most retrofit applications
Upload/download remotely or locally
Two-level maintenance alert reporting
Pre-alarm and alarm verification by point
Adjustable detector sensitivity
4 x 20 character backlit LCD display
Optional earthquake hardening: seismic Importance Factor 1.5
iO64 Intelligent
Life Safety System
7165-1657:
0244
S3000
COA 6020
Question and Answer IconNeed help?

Do you have a question about the EST iO64 and is the answer not in the manual?

Summary

Operation

Control Buttons

Details the functions of panel buttons for system operation and programming.

Wiring & Configuration

Notification Appliance Circuits

Details the specifications and wiring for notification appliance circuits (NACs).

Alarm, Trouble, and Supervisory Relay

Explains the relay outputs for alarm, trouble, and supervisory conditions.

Auxiliary & Smoke Power Outputs

Describes auxiliary power outputs used for ancillary equipment.

Signature Device Loop

Covers the single device loop for Signature Series detectors and modules.

Annunciator Loop

Details the connection for serial driven and supervised remote annunciators.

Option Cards

SA-232 RS-232 Interface

RS-232 interface for connecting printers or computers for configuration.

SA-CLA Class A Module

Provides Class A capability for NAC, loop, and annunciator wiring.

SMK Smoke Power Converter

Provides regulated power for two-wire smoke circuits.

SA-ETH Ethernet Interface Card

Ethernet connection for downloading configuration and viewing reports.

SA-DACT Dialer

SIGA-REL Releasing Module

Specifications

Ordering Information

Analog Addressable Devices & Accessories

Intelligent Detectors & Bases

Lists various intelligent detectors and their mounting bases.

Modules

Details different types of interface and control modules for the system.

Accessories

Lists various accessories like cabinets, printers, and software.

Summary

Operation

Control Buttons

Details the functions of panel buttons for system operation and programming.

Wiring & Configuration

Notification Appliance Circuits

Details the specifications and wiring for notification appliance circuits (NACs).

Alarm, Trouble, and Supervisory Relay

Explains the relay outputs for alarm, trouble, and supervisory conditions.

Auxiliary & Smoke Power Outputs

Describes auxiliary power outputs used for ancillary equipment.

Signature Device Loop

Covers the single device loop for Signature Series detectors and modules.

Annunciator Loop

Details the connection for serial driven and supervised remote annunciators.

Option Cards

SA-232 RS-232 Interface

RS-232 interface for connecting printers or computers for configuration.

SA-CLA Class A Module

Provides Class A capability for NAC, loop, and annunciator wiring.

SMK Smoke Power Converter

Provides regulated power for two-wire smoke circuits.

SA-ETH Ethernet Interface Card

Ethernet connection for downloading configuration and viewing reports.

SA-DACT Dialer

SIGA-REL Releasing Module

Specifications

Ordering Information

Analog Addressable Devices & Accessories

Intelligent Detectors & Bases

Lists various intelligent detectors and their mounting bases.

Modules

Details different types of interface and control modules for the system.

Accessories

Lists various accessories like cabinets, printers, and software.

Overview

The EST iO64 Intelligent Life Safety System is a sophisticated fire alarm control panel designed for small to mid-sized applications. It combines high-end intelligent processing with a user-friendly interface, offering advanced features for both building owners and contractors.

Function Description

The iO64 system provides comprehensive life safety management, including intelligent detection, electronic addressing, automatic device mapping, and optional Ethernet connectivity. It supports a single Class B analog device loop for up to 64 intelligent devices and two Class B Notification Appliance Circuits (NACs). Optional Class A device wiring is available with an SA-CLA module.

The system's front panel features a large backlit 80-character LCD display that shows system status, event details, and programming prompts. Large tactile control buttons and bright multi-color LEDs provide at-a-glance status indication and easy operation, even in low light conditions. Two fully-programmable front panel switch/LED combinations, with slide-in labels, offer additional flexibility for custom applications.

The iO64 is particularly well-suited for retrofit applications as all connections are made over standard wiring, eliminating the need for shielded cable and allowing the use of existing wiring to upgrade legacy control panels.

Key Features:

  • Intelligent Detection: Supports Signature Series modules and detectors, including multisensor detectors for reliable suppression.
  • Electronic Addressing and Automatic Device Mapping: Simplifies installation and ensures devices are correctly located on the system.
  • NACs: Two Class B NACs are standard, configurable for continuous, temporal, synchronized, latching, and coded output. Optional Class A wiring is available.
  • Relays: Includes Form C for Alarm and Trouble, and Form A for Supervisory relays.
  • Power Outputs: Two auxiliary power outputs for ancillary equipment like remote annunciators and two-wire smoke detectors.
  • Annunciator Loop: Supports up to eight serially driven and supervised remote annunciators (LCD, LED-only, and graphic interface).
  • Synchronization: Supports Genesis horn silence over two wires and UL 1971-compliant strobe synchronization.
  • Ethernet Connectivity (Optional): An optional Ethernet port (SA-ETH) allows for diagnostics, programming, and various system reports, as well as remote upload/download capabilities.
  • Programmable Switches: Two programmable switches with LEDs and custom labeling.
  • Display: 4 x 20 character backlit LCD display.
  • Earthquake Hardening (Optional): Seismic Importance Factor 1.5.

Operation Features:

The front panel controls include:

  • System Reset: Initiates a system reset.
  • ACK/Panel Silence: Silences the panel and remote annunciators during active trouble, supervisory, or alarm events, and acknowledges new event activations.
  • Signal Silence: Silences active notification appliances; pressing it a second time turns NACs back on.
  • Drill: Initiates a drill confirmation; pressing it a second time turns off the drill function.
  • Remote Disconnect: Disables or enables the dialer; if set to modem only, disables or enables the common alarm relay.
  • Navigation Arrows (Left, Right, Up, Down): Used for cursor movement, toggling programming selections, advancing through events, and navigating menus.
  • Enter: Displays selected event details, retrieves sub-menus, jumps to the Save function, and enters data.
  • Cancel: Exits detailed information displays, current menu levels, or clears current entries.
  • Menu: Enters or exits menu mode.
  • Space: Enters a space character.
  • Alphanumeric Keypad: Enters numbers or secondary values.
  • Programmable Buttons: Can be programmed to control outputs, disable devices, or unlatch system outputs.

Important Technical Specifications

System:

  • Device Loops: 1 loop Class B, Class A optional (with SA-CLA card), supporting up to 64 device addresses.
  • NACs: 2 Class B, Class A optional (with SA-CLA card), 2.5 amps each.
  • Primary Power: 3.75 A FWR total at 120/230 VAC 60 Hz; 3.0 A FWR total at 230 VAC 50 Hz.
  • NAC Operating Voltage: 24 VDC (min. 19.5 VDC @ 20.4 V battery voltage).
  • Loop Operating Voltage: 20 V peak-to-peak.
  • Aux Power 1 (Continuous): 24 VDC nominal at 500 mA.
  • Aux Power 2 (Resettable): 24 VDC nominal at 500 mA.
  • Base Panel Current Draw: Standby: 155 mA; Alarm: 204 mA.
  • Batteries: Sealed lead acid type only, max charging capacity 26 Ah. iO64 cabinets accommodate up to 10 A/H batteries; external cabinet for larger sizes.
  • Loop Circuit Max Detector Standby Current: 1.5 mA.
  • Compatibility ID: 100.
  • Environmental Temperature: 0 to 49°C (32 to 120°F).
  • Humidity: 0 to 93% RH, noncondensing.
  • Terminal Rating: All terminals rated for 12 to 18 AWG (0.75 to 2.5 sq mm).
  • Agency Listing: UL864, UL2017, CSFM, ULC, and NYFD COE#6020.

Option Cards:

  • SA-DACT (Dual Line Dialer/Modem): Supports 4/2 and Contact ID, mounts in cabinet on base plate.
  • SA-232 (Serial Port RS-232): For printers & computers, mounts in cabinet to base plate.
  • SA-ETH (Ethernet Port): Slave, mounts in cabinet on base plate.
  • SA-CLA (Class A Adapter Module): Provides Class A capacity on NACs, mounts in cabinet on main board.
  • D16L-IO-1 (LED Annunciator Module): 16 X 2-LED zones (4 max programmable for sup), mounts in cabinet to left of LCD display for zones 1-16.
  • D8RY-IO-1 (LED Annunciator Module): 16 X 2-LED zones (4 alarm only, 8 supervisory only, 4 alarm or supervisory), mounts in cabinet to left of LCD display for zones 1-16.

Remote Annunciators (LCD & LED):

  • Various models available (RLCD, RLCD-R, RLCD-C, RLCD-CR, etc.) offering 4x20 LCD displays, common indicators, and controls.
  • Serial Communications: Voltage: 2.55 V, Current: 30 mA max.
  • Max Drops: 8 drops max, RS-485 Class B, Class A.

Signature Series Modules:

  • SIGA-REL (Releasing Module): Analog addressable module for sprinkler, pre-action, deluge systems, and extinguishing agents.
    • Power Riser Input Voltage: 24 Vdc (power limited).
    • Release Circuits Output Rating: 2A @ 24 Vdc (per circuit), 4 valves max.
    • First Alarm Output Relay: 3 A @ 24 Vdc (0.6 power factor) Form C.
    • Supervisory Current: 1000 µA; Alarm Current: 1000 µA.

Maintenance Features

  • Two-Level Maintenance Alert Reporting: Provides detailed alerts for system maintenance needs.
  • Adjustable Detector Sensitivity: Allows fine-tuning of detector sensitivity to suit environmental conditions.
  • Pre-alarm and Alarm Verification by Point: Helps reduce false alarms by verifying alarm conditions.
  • System Reports: The iO-CU software allows access to various system reports, including correlation groups, device maintenance, device details, history, system configuration, walk test, CO runtime, internal status, system status, and dialer reports.
  • Remote Upload/Download: Configuration programs can be uploaded from or downloaded to the panel remotely or locally using the iO-CU software and optional RS-232 or Ethernet connections.
  • Automatic Device Mapping: Ensures devices are correctly located on the system, simplifying troubleshooting.
  • Diagnostic Tools: The optional Ethernet port and iO-CU software provide advanced diagnostic capabilities.

EST iO64 Specifications

General IconGeneral
BrandEST
ModeliO64
CategorySafety Equipment