66
P21 Minimum time between compressor Off and On 0 99 3 Min
Defrosting
P22
Type of Defrost
0 2 1 -
0 = electric
1 = hot gas
2 = air
P23 Evaporator Temperature for End of Defrost 0 2 8 °C
P24 Maximum Defrost duration 1 99 10 Min
P25 Delay between two Automatic defrosts in Storage 0 99 12 Ore
P26 Delay in defrost activation from the start of Storage 0 99 0 Min
P27 Enable Defrost at Blast chilling/Freezing Cycle start 0 1 0 -
P28 Draining time 0 99 2 Min
P29 Ignore compressor safety times in defrost 0 1 0 -
P30 Delay in compressor activation from defrost request 0 400 30 Sec
P31 Delay in solenoid valve activation from defrost request 0 400 35 Sec
Evaporator fan
P32 Evaporator temperature above which the Fans are locked in Storage -40 99 10 °C
P33 Hysteresis for restarting Fans -15 15 1 °C
P34
Enables use of fans in Defrost (for P22 equal to zero and/or one)
0 1 0 -0 = fans off during defrost
1 = fans active during defrost
P35 Duration of fans lock after draining 0 15 1 Min
P36 Threshold temperature for Fans Lock cell -40 99 90 °C
P37
Door opening effect on the fans
0 1 1 -0 = no effect
1 = stop fans
Digital inputs
P38
Door micro input polarity
0 1 0 -
0 = NO; 1 = NC
P39 Door opening signalling delay 0 200 0 Sec
P40
High Pressure Alarm input polarity
0 1 1 -
0 = NO; 1 = NC
P41 High Pressure Alarm Input Delay 0 200 120 Sec
P42
Low Pressure Alarm input polarity
0 1 0 -
0 = NO; 1 = NC
P43 Low Pressure Alarm Input Delay 0 200 0 Sec
P44
Thermal Compressor Alarm input polarity
0 1 1 -
0 = NO; 1 = NC
P45 Thermal Compressor Alarm input Delay 0 200 0 Sec
Sterilization
P46
UV Lamp Start Duration
0 99 20 Min
0 = disabled
Heating the Needle probe (not activated)
P47 Needle probe Heating Activation threshold -40 99 45 °C
P48 Duration of Needle probe heating 0 99 15 Sec
Door Frames
P49 Cell temperature threshold for Door Frame Activation -20 20 0 °C
P50 Hysteresis for door frame activation -10 10 2 °C
Condenser Fans
P51
Condenser fan management mode (only if condenser probe enabled)
0 1 1 -0 = in parallel with the compressor
1 = always active during the cycles