67
P52 Condenser temperature setpoint for Condenser Fan deactivation -45 100 15 °C
P53 Hysteresis for Restart of Condenser fans -10 10 5 °C
P54 Condenser Fans deactivation Delay from Compressor shutdown 0 300 30 Sec
General Congurations
P55 Duration of Buzzer Sound for end of cycle 0 99 3 Sec
P56 Duration of Buzzer Sound during an alarm 1 400 15 Sec
P57 Pump-Down Duration when Switching On and Off 0 999 5 Sec
P58 Base Times = 0 hours minutes ; 1 = minutes seconds 0 1 0 -
P59 Reserved - - - -
P60 Chooses Probe type 0 = NTC ; 1 = PTC 0 1 0 -
P61 Activation of Condenser Probe 0 1 1 -
Conguring the Condensation Temperature Alarm
P62 Condenser High Temperature Alarm Threshold (only if P61 = 1) 0 99 65 °C
P63 High condensation temperature alarm Hysteresis (only if P61 = 1) 0 30 10 °C
Minimum and Maximum Alarm Conguration
P64
Minimum Alarm Set for the Set-Point for Positive Storage
-99 0 0 °C
0 = alarm disabled
P65
Maximum Alarm Set for the Set-Point for Positive Storage
0 99 0 °C
0 = alarm disabled
P66
Minimum Alarm Set for the Set-Point for Negative Storage
-99 0 0 °C
0 = alarm disabled
P67
Maximum Alarm Set for the Set-Point for Negative Storage
0 99 0 °C
0 = alarm disabled
P68 Maximum and Minimum alarm Hysteresis 15 2 °C
P69 Maximum and Minimum Alarm Inhibition time from start of Storage 0 255 0 Min
P70 Maximum and Minimum Alarm Inhibition time 0 255 0 Min
HACCP Settings and printing
P71
Enable Printer
0 1 0 -
0 = disabled ; 1 = enabled
P72 Sampling Interval 0 60 15 Min
P73 Deletion of Alarms history 0 1 0 -
P74
Baud rate for PC communication
0 3 2 -
0 = 2400 ; 1 = 4800 ; 2 = 9600 ; 3 = 19200
P75
Parity for PC communication
0 2 2 -
0 = no parity ; 1 = odd ; 2 = even
P76 Address card for PC communication 1 247 1 -
Outputs conguration
P77
K6 output conguration
0 = core probe heating; 1 = defrosting resistance
0 1 1 -
Defrosting
P78 Defrosting setpoint 0 99 6 °C
P79 Defrosting differential 0 15 2 °C
P80 Defrosting duration 0 99 5 Ore
P81 Evaporator fans’ setpoint in defrosting -40 99 -40 °C
P82 Evaporator fans’ hysteresis in defrosting 1 15 2 °C
Sanication
P83 Core probe temperature for end of sanication’s rst phase -99 99 -20 °C
P84 Room setpoint for sanication’s rst phase -99 99 -50 °C
P85 Duration of sanication’s second phase 1 99 24 Ore