XP600/1100/2000 INSTALLATION AND OPERATION MANUAL
APPENDIX A
Page 12
XP-600 / 12VDC
13.8 VDC
10.4 / 10.6 VDC
16.5 VDC
51.2 A
99.9 A
XP-600 / 24VDC
27.6 VDC
19.0 / 21.0 VDC
33 VDC
25.0 A
49.3 A
XP-600 / 48VDC
55.2 VDC
41.5 / 42.5 VDC
62 VDC
18.5 A
26.5 A
XP-600 / 66VDC
75.9 VDC
57.5 / 58.5 VDC
91 VDC
12.5 A
24.3 A
XP-600 / 108VDC
124.0 VDC
94.0 / 95.0 VDC
149 VDC
9.0 A
17.5 A
MODEL
NORMAL
VDC
MINIMUM VDC
CUT-OFF / ALARM
MAXIMUM
VDC
RATED
CURRENT
AMPS
PEAK
CURRENT
AMPS
Input Power Requirements:
XP-1100 / 12VDC
13.8 VDC
10.4 / 10.6 VDC
16.5 VDC
5.6 A
10.9 A
XP-1100 / 24VDC
27.6 VDC
19.0 / 21.0 VDC
33 VDC
93.8 A
219.8 A
XP-1100 / 48VDC
55.2 VDC
41.5 / 42.5 VDC
62 VDC
45.8 A
108.4 A
XP-1100 / 66VDC
75.9 VDC
57.5 / 58.5 VDC
91 VDC
34.0 A
80.4 A
XP-1100 / 108VDC
124.0 VDC
94.0 / 95.0 VDC
149 VDC
22.9 A
53.5 A
XP-2000 / 12VDC
XP-2000 / 48VDC
XP-2000 / 66VDC
13.8 VDC
27.6 VDC
55.2 VDC
73.6 VDC
10.5 / 10.8 VDC
21.0 / 21.6 VDC
42.0 / 43.2 VDC
56.0 / 57.6 VDC
15 VDC
30 VDC
60 VDC
80 VDC
XP-2000 / 24VDC
XP-1100 / 32VDC
XP-600 / 32VDC
36.8 VDC
36.8 VDC
26.5 / 28.0 VDC
26.5 / 28.5 VDC
44 VDC
44 VDC
16.5 A
10.2 A
193.2 A
96.6 A
48.3 A
35.1 A
38.5 A
24.0 A
450.0 A
254.0 A
127.0 A
92.3 A
Note: Peak surge Amps occurs at surge wattage and low-line DC input.