The
controller can also be set to ON/OFF, PI, PD and P control mode. Set Pb = 0 for
ON/OFF control mode. Set ti = 0 for PD control mode. Set td = 0 fro PI control mode and ti,
td = 0 fro P control mode. The Hysteresis (dead band) for ON/OFF control operates as
follows:
ON
OFF
SP-HYST SP+HYST
SP
When the second control output (output 2) is used, the proportional band of output 2
and the dead band interact as detailed below:
Ou
tput
Heating Cooling
PV
Overlap Dead
Ba
nd Band
ERROR MESSAGE AND TROUBLESHOOTING