EasyManuals Logo

Extech Instruments 96VFL Instruction Manual

Extech Instruments 96VFL
14 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #9 background imageLoading...
Page #9 background image
48VFL & 96VFL v1.2 07/13
The
controller can also be set to ON/OFF, PI, PD and P control mode. Set Pb = 0 for
ON/OFF control mode. Set ti = 0 for PD control mode. Set td = 0 fro PI control mode and ti,
td = 0 fro P control mode. The Hysteresis (dead band) for ON/OFF control operates as
follows:
ON
OFF
SP-HYST SP+HYST
SP
When the second control output (output 2) is used, the proportional band of output 2
and the dead band interact as detailed below:
Ou
tput
Heating Cooling
PV
Overlap Dead
Ba
nd Band
ERROR MESSAGE AND TROUBLESHOOTING
netzerotools.com
netzerotools.com

Other manuals for Extech Instruments 96VFL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Extech Instruments 96VFL and is the answer not in the manual?

Extech Instruments 96VFL Specifications

General IconGeneral
BrandExtech Instruments
Model96VFL
CategoryController
LanguageEnglish

Related product manuals