8.
BPM.
Ballast resistor connection
terminals
Always install it vertically
R
Diagram
Connect either one of the two pins of the thermostat to +
24 V DC of the external power supply of the electrical
cabinet and the other one to a PLC input.
Important. Remember to manage the chosen PLC input
in the PLC program to generate an error when exceeding
the limit temperature (200 °C) detected by the sensor and
to open the contact.
Connect the R-R terminals of the
Ballast resistor ER+TH-18/1100 to the
connection terminals R1-R1 of the
Ballast connector of the bus protection
module, BPM.
External thermostat
Element to connect with
the external thermostat
R
ER+TH-18/1100
ER+TH-18/1100