8.
WARNING. Therefore, the resistor should be mounted away from the rest of
Connect the fan connection terminals to an
outlet of the electrical cabinet, single phase
50/60 Hz, 220/240 V AC. Consumption:
0.15/0.13 A, 23/20 W.
Ballast resistor
connection terminals
Tk connection
terminals of the
internal thermostat
Always install it vertically
Re
L+
Diagram
Connect either one of the two
pins to +24 V DC of the
external power supply of the
electrical cabinet and the
other one to a PLC input.
Important
. Remember to
manage the chosen PLC input
in the PLC program to generate
an error when exceeding the
limit temperature (160 °C)
detected by the sensor and to
open the contact.
Connect the Ballast resistor terminals to the Re and L+ terminals of the
terminal strip of the Ballast of the power supply or compact drive
accordingly.
Two FASTON
plug-in male
terminals with
a tab size of
2.8 x0.5 mm for
fan connection