Take the connection terminals of each fan to an outlet of the electrical cabinet, single
phase 50/60 Hz, 220/240 V AC. Consumption: 0.15/0.13 A, 23/20 W.
Always install both resistors vertically
Diagram for 2 resistors in parallel with fan and internal thermostat
Connect as shown in the image the terminal
labeled + 24 V DC to an external 24 V DC
power supply of the electrical cabinet and the
other one labeled PLC INPUT to a PLC input.
IMPORTANT.
Remember to manage the
chosen PLC input in the PLC program to
generate an error when exceeding the limit
temperature (160 °C) detected by the sensor
and to open the contact.
Connect as shown in the
image the indicated termi-
nals to the Re and L+ termi-
nals of the terminal strip of
the Ballast of the power sup-
ply (only PS-65A or XPS-
65).
Diagram for 2 resistors in parallel with an internal thermostat
and no fan
Connect as shown in the image the terminal
labeled +24 V DC to an external 24 V DC
power supply of the electrical cabinet and
the other one labeled PLC INPUT to a PLC
input.
IMPORTANT.
Remember to manage the
chosen PLC input in the PLC program to
generate an error when exceeding the limit
temperature (160 °C) detected by the
sensor and to open the contact.
Connect as shown in the image
the indicated terminals to the Re
and L+ terminals of the terminal
strip of the Ballast of the power
supply (only PS-65A or XPS-65).