OWNERS INSTRUCTIONS (Cont'd)
TROUBLE OPERATION OF THE FIRE ALARM SYSTEM CONTROL UNIT
A trouble is indicated by the following conditions:
The yellow SYSTEM TROUBLE L.E.D. lights in a pulsating manner.
The trouble buzzer sounds in a pulsating manner.
Depending on the type of trouble, a yellow zone TROUBLE L.E.D. or a yellow trouble
L.E.D. of an optional module may be lit.
If a remote station type of city connection is used, a trouble signal is sent to the remote
station(s).
If a remote trouble unit is used, the trouble is indicated at the remote location.
Optional trouble relays will also activate to serve various supplementary functions.
TO SILENCE THE TROUBLE BUZZER:
Push down the TROUBLE SILENCE switch to the silenced position.
Notify the proper personnel for servicing the system immediately.
Refer to SECTION IV - TROUBLESHOOTING GUIDE.
Upon repairing the trouble condition, if the trouble buzzer had been silenced, the trouble
buzzer will sound again until the TROUBLE SILENCE switch is returned to the normal
position.
SPRINKLER SUPERVISORY OPERATION OF THE FIRE ALARM SYSTEMS CONTROL UNIT.
(This applies only to control units that have been programmed for sprinkler supervisory switches).
A SUPERVISORY CONDITION IS INDICATED BY THE FOLLOWING CONDITIONS:
The Red Zone #1, Alarm L.E.D. lights.
The Yellow System Trouble L.E.D. flashes.
The trouble buzzer sounds.
If a remote annunciator or trouble unit is used,the alarm and/or trouble is also indicated at
the remote location.
If a supervisory remote station connection is used, a supervisory signal is sent to the remote
staion.
If an alarm remote station connection is used, a trouble signal is sent to the remote station.
If a zone relay module is used, the Zone #1, contact will transfer.
Optional trouble relays will also activate to serve various supplementary functions.
TO SILENCE THE TROUBLE BUZZER:
Push down the TROUBLE SILENCE SWITCH to the silenced position.
Locate the activated switch and return it to its normal position.
If the trouble buzzer has been silenced, the trouble buzzer will sound again until the
TROUBLE SILENCE SWITCH is returned to the normal position.
If a supervisory condition still exists, notify the proper personnel for servicing the system
immediately.