  • K
    kramerjackSep 23, 2025
    What does 'FDLC x EXT EE' mean on Faraday Control Unit?
    • J
      Jennifer BrownSep 23, 2025
      If the Faraday Control Unit displays 'FDLC x EXT EE', it indicates that the EEPROM of FDLC X is corrupted and requires replacement of the FDLC.
  • R
    Rebecca WhiteAug 25, 2025
    What does it mean if my Faraday Smoke Alarm displays BATT Trouble?
    • L
      Lindsey FischerAug 25, 2025
      If your Faraday Smoke Alarm displays 'BATT Trouble', it indicates that the battery input is either low or off. Check the battery connection and power level.
  • J
    Jennifer SavageAug 25, 2025
    What should I do if my Faraday Smoke Alarm shows NACxx Trouble?
    • K
      kevin76Aug 26, 2025
      If your Faraday Smoke Alarm displays 'NACxx Trouble', it means the NAC xx wiring is either open or shorted. Inspect the wiring for any issues.
  • L
    lauraleonardAug 27, 2025
    What to do if my Faraday Smoke Alarm shows CITY Trouble?
    • C
      Calvin RogersAug 27, 2025
      If your Faraday Smoke Alarm shows 'CITY Trouble', it indicates that the Local Energy circuit is open. Check the local energy circuit.
  • V
    vandersonAug 27, 2025
    What does DACT Acct Trb mean on my Faraday Smoke Alarm?
    • A
      ashleyjonesAug 28, 2025
      If your Faraday Smoke Alarm displays 'DACT Acct Trb', it means there is a DACT account reporting trouble.
  • M
    michael67Sep 15, 2025
    What does 'CHARGER SUPV Trouble' mean on my Faraday Control Unit?
    • D
      Dr. Erin HuffSep 15, 2025
      If your Faraday Control Unit displays 'CHARGER SUPV Trouble', it indicates that the battery charger voltage is too low. Check the voltage of the battery charger.
  • A
    Ashley GonzalezSep 12, 2025
    What does 'GRD FAULT Trb' mean on Faraday Control Unit?
    • J
      joseph00Sep 13, 2025
      If the Faraday Control Unit displays 'GRD FAULT Trb', it means the system has detected a positive or negative ground fault. Investigate the system for ground faults.
  • M
    Melissa SandersSep 14, 2025
    What to do if Faraday Control Unit displays 'PC Pgmr Trb'?
    • D
      deborah57Sep 14, 2025
      If your Faraday Control Unit is displaying 'PC Pgmr Trb', this indicates that the control unit is not receiving communication from the PC. Check the connection between the control unit and the PC.
  • J
    Jessica WalkerSep 5, 2025
    What does LCDxx Not Pgmd mean on my Faraday Smoke Alarm?
    • N
      Nathan ButlerSep 5, 2025
      If your Faraday Smoke Alarm displays 'LCDxx Not Pgmd', it means the LCD Annunciator xx is not programmed but is responding.
  • M
    Monica BakerSep 3, 2025
    What does LCDxx Trouble mean on my Faraday Smoke Alarm?
    • J
      James GrahamSep 3, 2025
      If your Faraday Smoke Alarm displays 'LCDxx Trouble', it means the LCD Annunciator xx reports trouble.