III- 47
Power Failure Contacts for a power limited source
Rated 1A. @ 28VDC. Resistive
Not Supervised by Control Unit
Form "C" contact configuration (contacts shown in
normal standby condition: transfer for operated
condition).
NOTES:
1.) Units to be installed in accordance with the
National Electrical Code and / or local
electrical codes.
2.) Terminal block will accept a maximum of
#14 AWG wiring or .260" spade terminals.
Terminal block screw size is #6-32.
3.) Maximum power output from the resettable
and non resettable power output is.3 Amps.
Power output is not supervised, special
application.
FARADAY DC-100/101
NOTE:
Wiring for DC-101 must be enclosed in
conduit and may not exceed 20 feet.
Trouble Contacts for a power limited source
Rated 1A. @ 28VDC. Resistive
Not Supervised by Control Unit
Alarm Contacts for a power limited source
Rated 1A. @ 28VDC. Resistive
Not Supervised by Control Unit
Supervisory Contacts for a power limited source
Rated 1A.@ 28VDC. Resistive
Not Supervised by Control Unit
Non Resetable Power Output,.3Amp Max.
Power Limited See Note 3
Not Supervised by Control Unit