EasyManua.ls Logo

Faraday 15220A - Section II Owners Instructions; Alarm Operation; Trouble Operation; System Testing and Maintenance

Default Icon
66 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
I - 3
15220A/15240A GENERAL SPECIFICATIONS
Normal Operating Ambient Temperature: 68°- 77°F (20°-25°C)
Extreme Ambient Temperature: 32°-120°F (0°-49°C)
up to 3 hours
Extreme Relative Humidity: 85% @ 86°F (30°C)
up to 24 hours
Primary Input Voltage:
15220A / 15240A 120VAC 50/60Hz Nominal
(102-132 VAC)
15220A-240 / 15240A-240 240VAC 50/60Hz Nominal
(204-264 VAC)
Maximum Primary Input Current: 2A.
Secondary and Trouble Power Supply: 24 Volt Battery Set
Maximum Charge Voltage: 27.8VDC
Maximum Charge Current: 1.6A.
Battery Capacity: 6-15 A.H.
Maximum Battery Input Current: 3.2A
Resettable Smoke Detector Power
Power Limited
Voltage Range: 24VDC Nominal
Current Output: Up to 0.3A (limited by
battery capacity)
Maximum Ripple: 1.2V
Initiating Circuits:
Power Limited
Style "B" (class "B")
Standby Voltage Range: 16-28VDC
Maximum Standby Current: 7.6 Ma.
Maximum Standby Detector Current: 3.0 Ma.
Maximum Alarm Current: 36 Ma.
Maximum Ripple: 1.2V
Maximum Wire Loop Resistance: 100 ohms
E.O.L. 3.9K Ohm 1/2 W. Resistor
Signal Circuits:
Power Limited
Style "Y" (Class "B")
Alarm Voltage Range: 24VDC Full Wave (nominal)
Maximum Alarm Current: 2.5A @ 24VDC
Maximum Alarm Ripple: 16V
Maximum Standby Current: 0.47 Ma. per circuit
Maximum Wire Loop Voltage Drop: 1.0VDC
E.O.L. Two 47K Ohm 1/2 W Resistors
LISTED TO UL 864 SEVENTH EDITION FILE #S-405