FGP50/MEVO
TECHNICALDATAFGP50/MEVO
OPERATINGRANGEDIAGRAMFGP50/MEVO
Fig. 2 X=ThermalpowerY=Pressioninthecombustionchamber
ThefiringrateshasbeenobtainedbasedontestboilersinaccordancewithEN267standardsandareindicativeofmatchingtheburnertothe
boiler.Forthecorrectoperationoftheburner,combustionchamberdimensionsmustbeinaccordancewithcurrentregulation.Incaseofnon-
compliance,contactthemanufacturer.
-1
1
3
5
7
9
11
13
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800
<kW>
<mbar>
)*30(92
*Referenceconditions:Environmenttemperature20°C-Barometricpressure1013mbars-Altitude0metre(sealevel).
MODEL
FGP50/MEVO
Thermalpowermin.1°st./min.2°st.-max.2°st.*[Mcal/h]107/204-542
Thermalpowermin.1°st./min.2°st.-max.2°st.*[kW]124/237-630
LIGHT-OILflowmin.1°st./min.2°st.-max.2°st.*[kg/h]10.5/20-53
Fuel:LIGHT-OIL1.5°Eat20°C=6.2cSt=35secRedwoodN°1
Intermittedworkingoperation(min.1stopevery24hours)twostagesprogressiveormodulating
Environmentalconditionsoperation/storage:-15...+40°C/-20...+70°C,rel.humiditymax.80%
Max.temperaturecombustionair[°C]60
Nominalelectricpower[kW]1.1
Fanmotor[kW]0.55
Pumpmotor[kW]0.37
Nominalfanmotorcurrentabsorption[A]1.4
Nominalpumpmotorcurrentabsorption[A]1.2
Nominalauxiliaryabsorption[A]0.6
Powersupply:3~400V,1/N~230V-50Hz
Electricprotectiondegree:IP44
LIGHT-OILBURNERSTWOSTAGESPROGRESSIVE
ORMODULATING