The following indoor coils and air handlers are designed and approved for use with the CH series units. Refer to the installation instructions
supplied with the indoor coils and air handler for installation detail. Some of the following information may not be included in those instructions
and is specific to the application of the CH series heat pump systems. If a different air handler is to be used with the matching indoor coil, refer
to the coil pressure-drop information for duct sizing requirements.
* Indoor pressure in inches based on dry coil. Increase pressure drop 25% for wet coil pressure drop.
All CH10 series outdoor units are shipped with pistons. Refer to Figure 1 on page 11 for proper installation.
* Indoor pressure based on dry coil. Increase pressure drop 25% for wet coil pressure drop.
All CH12 series units are to be matched with the air handler listed. These indoor units use a non-bleed-type expansion valve. Never use a
piston on the indoor coil when installing with a CH12 model unit. Refer to the instructions in Figure 2 on page 11 for installation of
expansion valve to indoor unit. TXV kits must be purchased as an accessory kit and are required to complete system installation.
10 FT. 15 FT. 25 FT.
CH1018B A24B1 E3009A16 600 .12
5
/16
5
/8
5
/16
5
/8
3
/8
3
/4
CH1024B A24B1 E3009A16 800 .20
5
/16
5
/8
5
/16
5
/8
3
/8
3
/4
CH1030B A30B1 E3612A16 1000 .20
5
/16
5
/8
5
/16
5
/8
3
/8
3
/4
CH1036B A36B1 E3618A16 1250 .24
5
/16
3
/4
3
/8
3
/4
3
/8
7
/8
CH1042C A48B1 E6016A20 1350 .21
5
/
16
3
/
4
3
/
8
3
/
4
3
/
8
7
/
8
CH1048C A48B2 E6026A20 1700 .30
3
/8
7
/8
3
/8
7
/8
3
/8
7
/8
CH1060C A60B1 E6037A21 1850 .29
3
/8
7
/8
3
/8
7
/8
3
/8
1
1
/8
MINIMUM RECOMMENDED TUBE O.D.
LIQUID LINE SUCTION LINE
REQUIRED
CFM
CONDENSER
MODEL NO.
AIR HANDLER
MODEL NO.
COIL MODEL NO.
(Included with
Air Handler)
INDOOR COIL
PRESSURE
DROP*
10 FT. 15 FT. 25 FT.
CH1218B A24B1 E3009A16 650 .11
5
/16
5
/8
5
/16
5
/8
3
/8
3
/4
CH1224B A24B1 E3009A16 800 .15
5
/
16
5
/
8
5
/
16
5
/
8
3
/
8
3
/
4
CH1230B A30B1 E3612A16 950 .15
5
/
16
5
/
8
5
/
16
5
/
8
3
/
8
3
/
4
CH1236B A36B2 E3618A16 1200 .20
5
/16
3
/4
3
/8
3
/4
3
/8
7
/8
CH1242C A42B1 E4824A20 1350 .26
5
/
16
3
/
4
3
/
8
3
/
4
3
/
8
7
/
8
CH1248C A60B1 E6037A21 1450 .30
5
/16
3
/4
3
/8
3
/4
3
/8
7
/8
CH1260C A60B1 E6037A21 1750 .25
3
/8
7
/8
3
/8
7
/8
3
/8 1
1
/8
MINIMUM RECOMMENDED TUBE O.D.
LIQUID LINE SUCTION LINE
REQUIRED
CFM
CONDENSER
MODEL NO.
AIR HANDLER
MODEL NO.
COIL MODEL NO.
(Included with
Air Handler)
INDOOR COIL
PRESSURE
DROP*
8
AIR HANDLER & EVAPORATOR MATCH-UPS