IMSS E3265
CONTROL PARAMETERS ALL 1MSS REMOTES
Table 5 - Control Parameters
Parameter Description
Control Setpoint
1 2 3 4 5 6 7 8 9
Compressor Cut out [°F]
30.0
28.0
26.0
24.0
22.0
20.0
18.0
16.0
14.0
Compressor Cut in [°F]
38.0°
Compressor Min On Time
5 min
Compressor Min Off Time
2 min
Compressor Max Run Time
60 min
Defrost Termination Temp [°F]
43.0
Time to first defrost
6 hr.
Time to subsequent defrost
6 hr.
Maximum Defrost duration
30 min
Defrost on demand differential [°F]
18.0
Delay for defrost on demand
5 min
Time delay to the next defrost on demand
30 min
\Table 6 - Temperature Probe Common Resistance Chart
Probe Temp
Maximum
Normal Resistance [Ω] Minimum Resistance [Ω]