After installation or cleaning it is recommended that a fire test is performed
1. On the Siemens Fire Control Panel (FCP), activate the ‘Detector test’ operating mode
The Detector Status indicator LED blinks amber twice every 4 seconds to indicate the test mode status.
2. Either cover the reflector slowly (>5 s) or hold the alarm test filter from the “S54331-S11-A1 FDL242 Commissioning Kit”
in front of the detector, such that it covers the detector optics.
The detector activates an alarm after around 5 seconds.
3. On the FCP, deactivate the “Detector test” operating mode
The detector is ready for operation.
If the alarm does not sound, check whether the standardized signal value is attenuated enough to reach the alarm threshold. Otherwise rotate the
alarm test filter a little or turn it round.
Activating the Test Alarm