11. Technical Specification
DC working power
Voltage range: 12V/24V (8-35V continuous)
Cranking drop outs: 0V for 100mS, assuming dc supply was at least 10V before dropout and recovers
to 5V
Max. operating current: @12V 180mA, @24V 90mA
Standby current: TBA
AC input voltage: phase voltage15-300Vac RMS (AC frequency40 Hz)
AC input frequency: 3-70Hz (voltage 15V)
Accuracy: 1%
Aux Control relay output: 3A/30Vdc
Start relay output: 3A/30Vdc
Fuel relay output: 3A/30Vdc
Protection: IP65 (when correctly installed)
Operating ambient temperature: -20 to 70
Storage ambient temperature: -30 to 80