Questions and Answers

  • R
    reginald91Aug 9, 2025
    What to do if the alarm relay is closed and the current output is at 20mA in my Fike Security Sensors?
    • E
      eric94Aug 9, 2025
      If the alarm relay is closed and the current output is at 20mA, it means that the detector is exposed to a flame. You should check the cause of the alarm. If it was caused by “friendly fire”, reposition the Fike Security Sensors detector so that it is not affected.
  • T
    Thomas LongAug 14, 2025
    Why is the yellow LED constantly on and the fault relay open in my Fike Security Sensors?
    • N
      nicholaswoodsAug 15, 2025
      If the yellow LED is constantly on and the fault relay is open, this indicates power problems. Check the voltage between the “24VDC (+)” and “24VDC (-)” terminals to verify that it is in the allowed range (see section 6.3).
  • F
    Frank DickersonAug 19, 2025
    What to do if the red LED is constantly on in my Fike Security Sensors?
    • K
      kathrynkingAug 19, 2025
      If the red LED is constantly on, the detector is in alarm latch mode. Restart the detector by turning the power off and then back on.
  • P
    philipturnerAug 25, 2025
    How to fix the Fike Security Sensors when the green LED is constantly on, the fault relay is closed, and there is no analog video?
    • J
      Joseph PonceAug 25, 2025
      If the green LED is constantly on, the fault relay is closed, and there is no analog video, it could be due to analog video not being configured properly or a wiring problem. Ensure the “Video Analog Output” setting is configured to NTSC or PAL (according to the CCTV system used). Also, check the video wiring and polarity.
  • H
    Heather AlvarezAug 29, 2025
    How to fix the Fike Security Sensors when the green LED is constantly on, the fault relay is closed, and there is no digital video (through ethernet)?
    • J
      Justin FosterAug 30, 2025
      If the green LED is constantly on, the fault relay is closed, and there is no digital video (through ethernet), it may be a wiring or software problem. Check the wiring and polarity. Also, check the ONVIF Client software.
  • D
    debramorrisSep 4, 2025
    What to do if the yellow LED is constantly on, the fault relay is open, and the current output is at 2mA in my Fike Security Sensors?
    • B
      Brittany NguyenSep 4, 2025
      If the yellow LED is constantly on, the fault relay is open, and the current output is at 2mA, it indicates a BIT Fault. You can clean the detector window and restart the detector by turning the power off and then back on.

Fike FIK-UV-IR-HD Series Specifications

General IconGeneral
IP RatingIP66
Detection TechnologyUV/IR
Field of View90°
Spectral ResponseUV: 185-260 nm, IR: 4.3 µm
Power Supply24 VDC
Alarm OutputRelay contacts, rated 2A @ 30 VDC