FIK-IR3-HD Triple IR Flame Detector

Questions and Answers

  • V
    Victoria RyanAug 8, 2025
    What to do if the alarm relay is closed and the current output is at 20mA in my Fike Security Sensors?
    • K
      Kathryn RussellAug 8, 2025
      If the alarm relay is closed and the current output is at 20mA, it means that the detector is exposed to a flame. You should check the cause of the alarm. If it was caused by “friendly fire”, reposition the Fike Security Sensors detector so that it is not affected.
  • D
    Dr. Ian GarnerAug 12, 2025
    Why is the yellow LED constantly on and the fault relay open in my Fike Security Sensors?
    • Y
      Yvonne DavilaAug 13, 2025
      If the yellow LED is constantly on and the fault relay is open, this indicates power problems. Check the voltage between the “24VDC (+)” and “24VDC (-)” terminals to verify that it is in the allowed range (see section 6.3).
  • M
    Michele HerreraAug 16, 2025
    What to do if the red LED is constantly on in my Fike FIK-IR3-HD Security Sensors?
    • M
      Michelle ParksAug 16, 2025
      If the red LED is constantly on, the detector is in alarm latch mode. Restart the detector by turning the power off and then back on.
  • T
    Trevor ReidAug 21, 2025
    How to fix the Fike FIK-IR3-HD Security Sensors when the green LED is constantly on, the fault relay is closed, and there is no analog video?
    • M
      Michael CarrilloAug 21, 2025
      If the green LED is constantly on, the fault relay is closed, and there is no analog video, it could be due to analog video not being configured properly or a wiring problem. Ensure the “Video Analog Output” setting is configured to NTSC or PAL (according to the CCTV system used). Also, check the video wiring and polarity.
  • E
    Erica ThomasAug 26, 2025
    How to fix the Fike Security Sensors when the green LED is constantly on, the fault relay is closed, and there is no digital video (through ethernet)?
    • J
      James WhiteAug 26, 2025
      If the green LED is constantly on, the fault relay is closed, and there is no digital video (through ethernet), it may be a wiring or software problem. Check the wiring and polarity. Also, check the ONVIF Client software.
  • K
    Kelly JohnsonAug 29, 2025
    What to do if the yellow LED is constantly on, the fault relay is open, and the current output is at 2mA in my Fike Security Sensors?
    • Q
      qdavisAug 29, 2025
      If the yellow LED is constantly on, the fault relay is open, and the current output is at 2mA, it indicates a BIT Fault. You can clean the detector window and restart the detector by turning the power off and then back on.
  • A
    andrew84Sep 2, 2025
    Why are the LEDs off and the fault relay open in my Fike FIK-IR3-HD Security Sensors?
    • L
      Laura AndersonSep 2, 2025
      If the LEDs are off and the fault relay is open, with a current output at 0mA, the unit is not receiving power. Here’s what you should do: * Check that the power is connected to the detector. * Check the power polarity. * Check the wiring in the detector.

Fike FIK-IR3-HD Specifications