• Supply Voltage: 12 to 24 VDC ± 10% regulated
• 2 x Current output:
- 4-20 mA, isolated, fully adjustable and reversible
- max loop impedance: 800 Ω @ 24 VDC - 250 Ω @ 12 VDC
• 2 x Solid State Relay output:
- user selectable as ON-OFF, Proportional frequency, Proportional Pulse,
Timed Pulse, Off
- optically isolated, 50 mA MAX sink, 24 VDC MAX pull-up voltage
- max pulse/min: 300
- hysteresis: User selectable
• 2 x Relay output:
- user selectable as ON-OFF, Proportional frequency, Proportional Pulse,
Timed Pulse, Off
- mechanical SPDT contact
- expected mechanical life (min. operations): 10
7
- expected electrical life (min. operations): 10
5
N.O./N.C.switching capacity
5A/240VAC
- max pulse/min: 60t
- hysteresis: User selectable
Environmental
• Operating temperature: -20 to +70°C (-4 to 158°F)
• Storage temperature: -30 to +80°C (-22 to 176°F)
• Relative humidity: 0 to 95% not condensing
Standards & Approvals
• Manufactured under ISO 9001
• Manufactured under ISO 14001
• CE
• RoHS Compliant
• GOST R