EasyManua.ls Logo

Fire-Lite FCPS-24FS6 - AC Loss Reporting Delay

Fire-Lite FCPS-24FS6
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
26 FCPS-24FS Series Instruction Manual — P/N 51883:H1 4/14/2011
Trouble Supervision AC Loss Reporting Delay
With SW1 switch 4 set to the ON position, AC Fail/brownout reporting will be delayed 2 hours
and the following trouble conditions will cause the normally energized Aux. Trouble Relay to
change states regardless of whether the panel is in alarm or standby:
An AC fail condition at the power supply
A battery fail condition at the power supply
A battery charger fail on the power supply
A ground fault condition on the power supply (zero impedance between the power supply
and ground
A field wiring fault on the NAC output of the power supply. (If the panel is in alarm, only a
short circuit on the NAC will be detected as a trouble)
With SW1 switch 4 set to the OFF position, AC Fail/brownout reporting will occur
immediately and the Aux. Trouble Relay will change state only for AC Fail/brownout
conditions. A monitor module can be used to monitor the relay for AC fail.
4.2 AC Loss Reporting Delay
The reporting of AC loss to a central station is usually delayed in order to prevent multiple trans-
missions of AC loss and restoral, thus allowing AC power to stabilize. When a host FACP is pro-
grammed to delay AC loss reporting, the FCPS-24FS must be configured to delay the reporting of
AC fail. This is accomplished by setting SW1 DIP switch 4 to the ON position. This will prevent
AC loss from being reported as a trouble condition for two hours.
Changing the AC Loss Reporting setting will also affect the functioning of the Trouble Relay.
Refer to “Aux. Trouble Relay/AC Fail Relay” on page 25.
Note that the FCPS-24FS power supply will immediately indicate loss of AC power by turning off
the AC Power LED and turning on the Charger Trouble/AC Loss LED, regardless of the setting of
SW1 DIP switch 4.
NOTE: The NAC Trouble LED will indicate which NAC circuit is in trouble by blinking once for
Circuit 1, twice for Circuit 2, three times for Circuit 3 and four times for Circuit 4. If more than one
circuit is in trouble, the LED will blink the highest circuit number in trouble.
SLC
Monitor Module*
Aux. Trouble Relay
Monitor Module ELR
FCPS-24FS6/8
T7
T6
NO
NC
*If the SLC device does not
match the one in this figure, refer
to the SLC manual wiring con-
version charts for legacy and
newer versions of the modules.

Table of Contents

Related product manuals