P. Description
37 Battery output voltage control output (connec
-
ted at factory)
38 Thermal probe jack
39 Switching-power-supply jack (connected at
factory)
40 Buzzer
41 Terminal board
42 Extinguishment Module anchor holes
43 Address Jumper:
// = Extinguishment Module no. 1
oo = Extinguishment Module no. 2
44 Terminal board
45 Cable: connects the Switching power supply
to the Main board (connected at factory)
46 Switching-power-supply anchor
47 Switching-power-supply closure rivet
48 Mains indicator LED
49 Switching-power-supply anchor hole
50 Switching-power-supply output voltage con
-
trol input (connected at factory)
51 Fine trimmer for the Switching-power-supply
output Voltage
52 Auxiliary power-supply terminals (27.6 V)
53 Mains power terminals (230V/50Hz)
54 Switching-power-supply screws
55 Switching-power-supply fuse — protects aga
-
inst overload:
J408 = F 2A 250V
J424 = F 3.15A 250V
56 Jack for Extinguishment Module nr. 2 or the
Display Module
57 Microprocessor
58 Jack for the Main board or Display Module
59 Reserved Jumper — DO NOT REMOVE
60 Battery jacks
61 Jumper for Ground (Earth) fault detection:
// = Ground (Earth) fault monitored
oo = Ground (Earth) fault NOT monitored
62 Jumper — to be REMOVED when connecting
a 4-20 mA gas detector to terminal Z1
63 Jack for Extinguishment Module nr. 1 or the
Display Module
64 Expander Module jack
65 Programming Jumper:
PRG PRG
oOProgramming
O Programming O Enabled
O Disabled o
66 Expander Control board jack (connected at
factory)
67 RS232 Serial Port
18 Conventional Fire Panels J424/J408