EQUIPMENT: FIRECLASS PRECEPT EN
PUBLICATION: FIRECLASS PREC EN INST
ISSUE No. & DATE: 3 13/09/18
PAGE 20 of 30
13. User Indications
General Indicator Section
Illuminates Steady for Mains or Standby power On.
Flashes on any new fire alarm condition, changing to a steady
indication on operation of Silence Alarms.
Illuminates Steady when the Fire Routing Output is active.
Flashes for any fault condition.
Flashes for mains or standby power supply/charge fault
Illuminates Steady to indicate Microcontroller or Memory Failure.
Flashes to indicate Engineer’s Configuration Mode active.
Flashes for any positive or negative power supply earth fault.
Flashes for any auxiliary supply fuse failure
Flashes for any Repeater fault or repeater communication fault,
Flashes for any sounder fault. Steady for sounders disabled.
Illuminates Steady while sounder walk test is active.
Fire Protection
Fault/Disabled
Flashes for a fault on the Fire Protection Output. Steady when Fire
Protection Output is disabled.
Fire Routing
Fault/Disabled
Flashes for a fault on the Fire Routing Output. Steady when Fire
Routing Output is disabled.
Fault Routing
Fault/Disabled
Flashes for a fault on the Fault Routing Output. Steady when Fault
Routing Output is disabled.
POWER SUPPLY ON
FIRE
FIRE ROUTING ACTIVE
GENERAL FAULT
POWER SUPPLY FAULT
SYSTEM FAULT
EARTH FAULT
FUSE FAILED
REPEATER FAULT
SOUNDER FAULT/DISABLED
SOUNDER TEST
FIRE PROTECTION FAULT/DISABLED
FIRE ROUTING FAULT/DISABLED
FAULT ROUTING FAULT/DISABLED
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
O I
FIRE
1. THE RED ZONE INDICATOR
WILL PULSE SHOWING THE
LOCATION OF THE FIRE.
2. CARRY OUT THE
REQUIRED FIRE DRILL.
3. TO SILENCE ALARMS
PRESS SILENCE ALARMS.
4. TO RESET FROM THE FIRE
CONDITION PRESS RESET.
FAULT
1. DETERMINE THE CAUSE
OF THE FAULT.
2. PRESS SILENCE BUZZER.
3. CALL YOUR SERVICE
ENGINEER.
SYSTEM FAULT
THE PANEL IS INOPERATIVE.
ARRANGE FOR
ALTERNATIVE FIRE
DETECTIN MEASURES.
EVACUATE
SILENCE/
RESOUND
ALARMS
RESET
SILENCE
BUZZER
DELAY
ON/OFF/
OVERRRIDE
SELECT
ON/OFF
TEST DISPLAY
ENABLE
DISABLE
TEST
SELECT
DISABLEMENT AND TEST
1. PRESS SELECT ON/OFF.
THE LED WILL ILLUMINATE.
2. SELECT THE ZONE OR
OUTPUT USING ↑ AND ↓. THE
FAULT LED WILL PULSE.
3. PRESS DISABLE OR TEST.
4. TO RE-ENABLE, SELECT
THE ZONE OR OUTPUT AND
PRESS ENABLE.
04:45:34
D/N ON
Zone Location Indications
Flashes when zone is in a fire condition, turning to steady on
operation of Silence Alarms.
Flashes when zone is in a fault condition. Illuminates steady when
zone is disabled or in test.
Access Controls Keyswitch:
O – Controls Locked
I – Controls Unlocked
Clock Module [Optional]:
Showing time and Day/Night ON
Back light flashes for Clock Module fault.