INDICATORS COLOUR INDICATION
COMMON FAULT Yellow On when a fault condition has occurred, or if
no other fault Led is on, this indicates 24v
auxiliary fuse failure.
COMMON FIRE Red On when a FIRE condition has occurred or
EVACUATE has been operated.
ZONES 1-4 FAULT Yellow Flashes if a detector is removed from its base,
or an open/short circuit zone wiring fault.
Illuminated when a zone is disabled and
flashes when in walktest.
ZONES 1-4 FIRE Red Illuminated during a FIRE condition in this
zone. Flashes when a device is being tested
during walktest.
SUPPLY Green Illuminated while power is being supplied to
the panel.
SUPPLY FAULT Yellow Flashes during a mains or battery supply
failure.
ALARM FAULT/ Yellow Flashes when a fault on the sounder wiring
DISABLED occurs. Illuminated if alarm lines are disabled.
DISABLED Yellow Illuminated when Zones and/or alarm are
disabled. The specific zone or alarm fault led
will also be lit.
TEST Yellow Illuminated when Walktest function selected.
SYSTEM FAULT Yellow Illuminated if the panel has malfunctioned and
an attempt to reset the system automatically
has been made. Flashes if an error in the
system software has been detected – Requires
attention.
ALARM SILENCED Yellow Illuminated if the sounders on the alarm
circuits during a fire/evacuation condition
have been switched off or silenced.
EARTH FAULT Yellow Will flash if a fault occurs with the earthing.