Follow below instruction for leak test:
1.Connect the Quick Connect Adapter to Natural Gas (NG) Piping. Make sure there is a NG Shut
Off Valve present (Figures 3 and 4). Make sure the Quick Connect Hose Assembly is NOT
connected to the Adapter before proceeding.
Figure 3 Figure 4
The thread size and type of the fittings and connections shall be compatible with each other. Use
NG resistant pipe sealant(dope) on all NG threaded connections.
3. Check all the connections and joints with ammonia free soapy water solution or leak detection
solution. Bubbles that appear to grow in size are the indication of a gas leak (Figures 5 and 6).
2. Turn on gas supply.
Figure 5
Figure 6
4. If there is a leak, turn off the gas and then tighten fittings until bubbles do not appear at the joints.
Reapply gas resistant pipe sealant(dope) as needed.
Do not attempt to use the Hose until all gas leaks have been repaired.
English Customer Service: 1-844-FIRMAN1
03
NOTICE: The male outlet must be 1/2" NPT . If not ,additional fittings will be needed to complete
the installation. The additional fittings are not included.
Quick Connect Adapter
Pipe Nipple
NG Shut Off Valve
NG Piping