Types 1301F and 1301G
4
!
WARNING
A regulator may vent some gas to the 
atmosphere.  In hazardous gas service, 
vented gas may accumulate, causing 
personal injury or equipment damage 
due to re or explosion.  Vent a regulator 
in hazardous gas service to a remote, 
safe location.
The optional brass spring case of the Type 1301F 
regulator has one 1/4 NPT internal connection.  
The Type 1301G regulator spring case has one 
1/8 NPT internal connection with a screen. To remotely 
vent the spring case, remove the screen, if present, and 
connect 1/4 or 1/8 NPT piping or tubing to the spring 
case connection.  The piping or tubing should vent the 
spring case to a safe location, have as few bends as 
possible, and have a screened vent on its exhaust end.
Each regulator is factory-set for the pressure setting
specied on the order.  If no setting is specied, 
outlet pressure is factory-set at the midpoint of the 
regulator spring range.  If pressure adjustment is 
necessary, refer to the Startup section.  In all cases, 
check the spring setting to make sure it is correct for 
the application.
Overpressure Protection
The 1301 Series regulators have an outlet pressure 
rating lower than their inlet pressure rating.  If actual 
inlet pressure can exceed the outlet pressure rating, 
outlet overpressure protection is necessary.  However, 
overpressuring any portion of the regulators beyond 
the limits in Specications section may cause leakage, 
damage to regulator parts, or personal injury due to 
bursting of pressure-containing parts.
Some type of external overpressure protection should be 
provided if inlet pressure will be high enough to damage 
downstream equipment.  Common methods of external 
overpressure protection include relief valves, monitoring 
regulators, shutoff devices, and series regulation.
If the regulator is exposed to an overpressure 
condition, it should be inspected for any damage that 
may have occurred.  Regulator operation below these 
limits does not preclude the possibility of damage from 
external sources or from debris in the pipeline.
Startup
With installation completed and downstream 
equipment adjusted, slowly open the upstream and 
downstream block valves while using pressure gauges 
to monitor pressure.
If adjustment is necessary, remove the closing cap, 
and, if one is used, loosen the locknut (key 18, 
Figures 3 and 4), and turn the adjusting screw (key 15, 
Figures 3 and 4) clockwise to increase the set 
pressure or counterclockwise to decrease the set 
pressure.  Monitor pressure with gauges during 
adjustment.  When adjustment is complete, tighten 
the locknut, and, if one is used, replace the closing 
cap.  If the desired outlet pressure is not within the 
range of the regulator spring, install a spring with a 
desired range according to the Maintenance section.
Shutdown
First, close the upstream shutoff valve, and then, 
close the downstream shutoff valve.  Next, open the 
vent valve between the regulator and the downstream 
shutoff valve and open the vent valve between the 
regulator and the upstream shutoff valve.  If vent 
valves are not installed, safely bleed off both inlet and 
outlet pressures and check that the regulator contains 
no pressure.
Maintenance
Regulator parts are subject to normal wear and 
must be inspected and replaced as necessary.  
The frequency of inspection and parts replacement 
depends on the severity of service conditions and 
the requirements of local, state, and federal rules 
and regulations.
Instructions are given below for disassembly and 
assembly of parts.
!
WARNING
To avoid personal injury or equipment 
damage from sudden release of 
pressure or explosion of accumulated 
gas, do not attempt any maintenance 
or disassembly without rst isolating 
the regulator from system pressure 
and relieving all internal pressure 
from the regulator.