startRegister Address of the rst Modbus register: 0 to 65535
Size Length of the response excluding header and CRC (in bytes): 1 to 250
enableReading Activation of read requests:
0 => enabled in instantaneous mode (parameters)
1 => enabled in polling mode (measurements)
2 => disabled
enableWriting Activation of write requests:
0 => write enabled with read before write
1 => write enabled, without read
2 => disabled
option1 Reserved for future use
option2 Reserved for future use
The declaration table for variables, named “Modbus_VariablesTables”. Each entry in this table
is dened by 12 elds separated by semicolons.
CHAMP DESCRIPTION
index Description, index for the variable, from 1 to N
indexRequest Designation of the Modbus request, dened in the table Modbus_
RequestsTables.
name Designation of the Modbus variable.