contact@webdyn.com | webdyn.com
V1.0 subject to changes | Webdyn © by Flexitron Group
FTP_Option Enable/Disable of two-
phase data uploading.
(File with extension “.tmp”
uploaded, then extension
“.tmp” deleted after
transfer.
0=Disabled; 1=Enabled
0 X
CONFIG_ForceUpload Allow overwriting
conguration and denition
les on the server if a local
change is performed to a
le parameters concerned:
0 = Off; 1 = Enabled
1 X
WebService_Enable Enable/Disable of web
services:
0= Disabled; 1= Enabled
0 X
WebService_Url Web Service http:// address
(up to 29 characters)
X
Language Language chosen for built-in
website:
fr = French; en= English
fr X
These variables can be modied at any time on the remote server.
The server conguration always overrides the local conguration via the web interface. Please
ensure that the two congurations are consistent.
To ensure consistency between the server and the unit, it is advisable to delete the unit’s
conguration le prexID_cong.ini from the remote server before any local modication is carried out.
Thus, the gateway will upload its new prexID_cong.ini conguration le at the next connection to the
FTP server rather than downloading the one present on the remote server. This would cause any
modication brought to the conguration via the web interface to be overridden.
6.2.1 Conguration via the Built-in Web Server
Access to the built-in Web interface on the WebdynModbus gateway is provided via the gateway’s LAN
connection. An Ethernet crossover cable must be used if a direct connection is made between the
computer and the gateway. In addition, both the computer used and the gateway must belong to the
same local network. If the WebdynModbus gateway has a static IP address (the default situation), the