etc. The metal objects or electronic devices can
interfere with the RF communication.
4. Do not mount onto metal wall boxes.
Installation, Mounting:
Warning:
-
Switch off the thermostat and any connected electric
sources before installing or performing maintenance.
-
This product is for fixed wiring only.
-
Must be wired in accordance with IET regulation.
Installation Location:
The thermostat (Receiver and Transmitter) should be
mounted on an inner wall 1.5m above the floor in a
position where it is readily affected by changes of the
general room temperature with freely circulating air.
Prevent direct exposure to sunlight; dripping or splashing
area. Do not place this unit at a location where air
circulation is low, or where it has great temperature
changes (e.g. near door).
3
Jumper selection:
Delay / No Delay jumper:
Heater Cooler
No delay 10sec 4mins
Delay 4mins 4mins
Choose the Delay option if compressor heat is
connected.
12-hours / 24-hours mode jumper:
When the 12-hours option is selected, the time is
shown in 12-hours mode. Otherwise, the time is
shown in 24-hours mode.
Heater / Cooler jumper:
Select the heater option when a heater is connected to
the receiver. Select the cooler option when a cooler is
connected to the receiver.
Address setting:
In the transmitter and receiver, there are dip switches to
select the addresses. The receiver ignores messages
which are sent by a transmitter with a different address
setting.
12