Issue/Rev. 0.1 (9/13) ║ MNFL003 • Page 7
microFlow.net Liquid Modbus Communications Manual Introduction
Mode dependent on EIA 232/EIA 485 wiring configuration. Must match
the master device.
Return to the Main Menu by pressing the <Clear> key.
1.5 Configuring the microFlow.net Liquid for Modbus Communications via
TCP/IP (Ethernet or SLIP)
Press <Enter> at the Ready screen to access the Main Menu
From the Main Menu, select Program Mode Menu and press <Enter>
Enter the Access Code when prompted and press <Enter>
From the Program Mode menu, select Comm. Directory and Press <Enter>
Select Host Interface and press <Enter>
From the Host interface Menu set the following items:
Host Interface
IP Address: 192.168.0.1
Net mask: 255.255.255.0
Gateway: 192.168.0.10
Ethernet Control: Poll and Program
-->Comm Link: Level 3
Return to the Main Menu using the <Clear> key
To access Modbus/TCP on microFlow.net Liquid connect to the standard Modbus/
TCP port 502 via the Ethernet port or a serial port configured for SLIP.