Control relay setup
29
Response current setting 400 V AC mains voltage
Current
transfor-
mer
Step size (= Rating of smallest stage kvar)
A/A 2.5 5 6.25 7.5 10 12.5 15 20 25 30 40 50 60 100
30/5 0.40 0.80 0.98 1.20 1.60
40/5 0.30 0.60 0.74 0.90 1.20 1.50
50/5 0.24 0.48 0.59 0.72 0.96 1.20 1.44
60/5 0.20 0.40 0.49 0.60 0.80 1.00 1.20 1.60
75/5 0.16 0.32 0.39 0.48 0.64 0.80 0.96 1.28 1.60 1.92
100/5 0.12 0.24 0.30 0.36 0.48 0.60 0.72 0.96 1.20 1.44 1.92
150/5 0.08 0.16 0.20 0.24 0.32 0.40 0.48 0.64 0.80 0.96 1.28 1.60 1.92
200/5 0.06 0.12 0.15 0.18 0.24 0.30 0.36 0.48 0.60 0.72 0.96 1.20 1.44
250/5 0.05 0.10 0.12 0.14 0.19 0.24 0.29 0.38 0.48 0.58 0.77 0.96 1.15 1.92
300/5 0.04 0.08 0.10 0.12 0.16 0.20 0.24 0.32 0.40 0.48 0.64 0.80 0.96 1.60
400/5 0.03 0.06 0.08 0.09 0.12 0.15 0.18 0.24 0.30 0.36 0.48 0.60 0.72 1.20
500/5 0.02 0.05 0.06 0.07 0.10 0.12 0.14 0.19 0.24 0.29 0.38 0.48 0.58 0.96
600/5 0.04 0.05 0.06 0.08 0.10 0.12 0.16 0.20 0.24 0.32 0.40 0.48 0.80
750/5 0.03 0.04 0.05 0.06 0.08 0.10 0.13 0.16 0.19 0.26 0.32 0.38 0.64
1000/5 0.02 0.03 0.04 0.05 0.06 0.07 0.10 0.12 0.14 0.19 0.24 0.29 0.48
1500/5 0.02 0.02 0.03 0.04 0.05 0.06 0.08 0.10 0.13 0.16 0.19 0.32
2000/5 0.02 0.03 0.04 0.05 0.06 0.07 0.10 0.12 0.14 0.24
2500/5 0.02 0.03 0.04 0.05 0.06 0.08 0.10 0.12 0.19
3000/5 0.02 0.03 0.04 0.05 0.06 0.08 0.10 0.16
4000/5 0.02 0.03 0.04 0.05 0.06 0.07 0.12
5000/5 0.02 0.03 0.04 0.05 0.06 0.10
6000/5 0.02 0.03 0.04 0.05 0.08
Table 2 Response current setting with 400 V AC mains voltage