EasyManua.ls Logo

Franke FFD090X5S - Page 12

Franke FFD090X5S
33 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 1 Ready, set up, go
12
Using a flexible connection
This appliance is approved for connection with a flexible hose, which complies with the AS/NZS
1869 (Australian Approved), 10mm ID, class B or D, between 1-1.2m long. Connection shall be in
compliance with AS/NZS 5601 for a high level connection. The hose should not be subjected to
abrasion, kinking or permanent deformation and should be able to be inspected along its entire length.
Unions compatible with the hose fittings must be used and connections tested for gas leaks. The fixed
consumer piping outlet should be at approximately the same height as the cooker connection point,
pointing downwards and approximately 150mm to the side of the cooker. The hose should be clear of
the floor when the cooker is in the installed position.
When installing the hose restraint device, the appliance anchor point is the rear panel.
Using a Copper Pipe connection
The cooker must be connected to the gas supply with upstream connection of an isolation valve in
accordance with the respectively valid regulations. We recommend that the isolation valve be fitted
prior to the cooker to enable isolation of the cooker from the gas supply. The valve must be easily
accessible at all times. To find out the gas type factory settings, see label on the rear of the appliance.
Test the operation of the cooker before leaving
Note: These burners have no aeration adjustment.
Check correct operation of the ignitions system and operation of the regulator and operation of the
burners individually and in combination. Burner flames should be clear blue, with no yellow tipping.
If the burners show any abnormality check that the burners are correctly located. If satisfactory
performance cannot be obtained, contact service.
Important
Before leaving instruct the owner in the use of the
cooker it should be expressly noted that we cannot
accept any liability for direct or indirect damage
caused by wrong connection or improper installation.
When being repaired, the appliance must always be
disconnected from the mains supply; if required,
notify our customer service.
Burners Gas type Pressure (kPa) Injector (mm) Mj/hr By-pass size (mm)
Small Natural 1.00 0.90 4.00 0.30 regulated
Small ULPG 2.75 0.54 4.00 0.30
Medium Natural 1.00 1.18 7.00 0.36 regulated
Medium ULPG 2.75 0.70 7.00 0.36
Large Natural 1.00 1.55 11.50 0.52 regulated
Large ULPG 2.75 0.92 11.50 0.52
Wok Natural 1.00 1.80 14.50 0.65 regulated
Wok ULPG 2.75 1.02 14.50 0.65
Wok 2way Natural 1.00
Ex. 1.80
int. 0.50
17.50
Ex. 0.65 reg.
int. 0.34 reg.
Wok 2way ULPG 2.75
Ex. 1.02
int. 0.50
17.50
Ex. 0.65 reg.
int. 0.34 reg.
Oven Natural 1.00 1.95 16.50 0.62 regulated
Oven ULPG 2.75 1.10 16.50 0.62
TABLE N°1
Adaption to various types of gas
Burners Dimensions (mm)
Auxiliary ø50
Semi-rapid ø70
Rapid ø95
Wok ø125
Wok 2 ways ø135
TABLE N°2: GAS BURNER DIMENSION

Related product manuals